Oxygen detectors – URS40SL 

11/04/2011 

Gas detection systems for industrial environments 

4/4

 

Checklist after 
mechanical and 
electrical installation 

 
 
 
 
 

Before using the sensor it must be recognised by the Control Unit through an 
assignment operation (refer to the manual of the aforesaid Control Unit for correct 
execution). 

The sensors are factory calibrated so they normally do not require any other calibration 
once installed. Still, after installation, an operational check of the sensors is 
recommended. 

The status LED means the following: 

• 

Flashing at 2Hz 

NOT ASSIGNED 

• 

Flashing about every 10 sec  

ASSIGNED AND WORKING 

• 

Steady  

ALARM 

 

Maintenance

 

Routine 
 

Corrective 

 
 
 
 
 
 
 

Decommissioning

 

A sensor functional test should be carried out every three-six months. 

Routine maintenance involves repeating the same tests as set forth in “checklist 
after mechanical and electrical installation”.

 

If any abnormalities are found during routine sensor maintenance, return the sensor 
concerned to the supplier / installer, who in turn will send it back to the 
manufacturer. 
Sensors may need to be re-calibrated, using the 

TUL40..

 calibration kit and the 

TUS40-40

 handheld terminal, which must be connected to the sensor via the 

communication on the Power supply and BUS connector. 

 

For the re-calibration procedure, see the instructions supplied with the handheld 
terminal. 

Remove power from the detector, disconnect all wiring and conduits and dismount 
the housing from all the blocking systems. 
 

Warranty 

Warranty on EsiWelma products is valid for 12 months from installation date and 
no longer than 24 months from manufacturing date on the product. Installation 
data, stamp and signature on the data sheet filled in by the installer will be 
considered proof for warranty. 

 

A copy of the warranty data sheet must be sent when returning the product under 
warranty. 

 

Accessories 

TUL40..

Gas calibration Kit 

TUS40

 Handheld terminal 

CRG40

 Gas collecting cone 

PAP40

 Powerful jets protection 

 

Dimensions and weight 

 

Dimensions (HxWxD): 130x100x60mm.                                                Weight: 0.5Kg

 

 

 