EsiWelma Srl 

URD40SE - EW0526D1_en.docx 

CO

2

 gas detectors – URD40SE 

16/06/2017 

Gas detection systems for industrial environments 

4/4

 

 

Checklist after 
mechanical and 
electrical installation 

 
 

 
 

 

Before  using  the  sensor  it  must  be  recognised  by  the  Control  Unit  through  an 
assignment  operation  (refer  to  the  manual  of  the  aforesaid  Control  Unit  for  correct 
execution). 

The sensors are factory calibrated so they normally do not require any other calibration 
once  installed.  Still,  after  installation,  an  operational  check  of  the  sensors  is 
recommended. 

The status LED means the following: 

 

Flashing at 2Hz 

NOT ASSIGNED 

 

Flashing about every 10 sec  

ASSIGNED AND WORKING 

 

Steady 

 

ALARM 

 

Maintenance

 

Routine 
 

Corrective 

 
 
 
 
 
 
 

Decommissioning

 

A sensor functional test should be carried out every three-six months. 

Routine  maintenance  involves  repeating  the  same  tests  as  set  forth  in  “checklist 
after mechanical and electrical installation”.

 

If any abnormalities are found during routine sensor maintenance, return the sensor 
concerned  to  the  supplier  /  installer,  who  in  turn  will  send  it  back  to  the 
manufacturer. 
Sensors may need to be re-calibrated, using the 

TUL40..

 gas calibration kit and the 

TUS40-40

  handheld  terminal,  which  must  be  connected  to  the  sensor  via  the 

communication on the Power supply and BUS connector. 

 

For  the  re-calibration  procedure,  see  the  instructions  supplied  with  the  handheld 
terminal. 

Remove power from the detector,  disconnect all  wiring and conduits and dismount 
the housing from all the blocking systems. 
 

Warranty 

Warranty  on  EsiWelma  products  is  valid  for  12  months  from  installation  date  and 
no  longer  than  24  months  from  manufacturing  date  on  the  product.  Installation 
data,  stamp  and  signature  on  the  data  sheet  filled  in  by  the  installer  will  be 
considered proof for warranty. 

 

A copy of the warranty data sheet must be sent when returning the product under 
warranty. 

 

Accessories 

 
TUL40..

 Gas calibration Kit 

TUS40

 Handheld terminal 

CRG40

 Gas collecting cone 

PAP40

 Powerful jets protection 

 

Dimensions and weight 

 

Dimensions (HxWxD): 164x100x82mm.                                            Weight: 0.8Kg 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 