URD40SE - EW0526D1_en.docx 

CO

2

 gas detectors – URD40SE 

16/06/2017 

Gas detection systems for industrial environments 

3/4

 

 

Installation 

The relative density of carbon dioxide is about one and a half times that of air, so it 
tends to collect at floor level in closed, unventilated environments. 

Therefore, the sensor must be installed about 30 cm above the floor level. 

Take  into  consideration  the  following  specific  installation  guidelines,  as  well  as  the 
above instructions, for location of the detectors. 

The detectors must be installed: 

1.  where accidental gas leakages are possible 
2.  at least 1.5m away from heat sources or from vent holes 
3.  not in spaces where ventilation is poor and where gas pockets may form 
4.  away from hindrances to natural gas flow 
5.  away  from equipment that may leak gas during normal operations 
6.  in  environments  with  a  temperature  range  of  -20°C  to  50°C  and  relative 

humidity below 90% (non-condensing) 

7.  Disconnect  equipment  from  the  power  supply  when  mounting  and  dismantling 

detectors. 

 

Special 
recommendations

 

CAUTION:  

safety is guaranteed only if cover is screwed on tight. 

-

  Tighten the cover clockwise, and when it is screwed on, make sure that there is 

no  more  than  0.5  mm  between  housing  and  cover.  This  guarantees  that  it  is 
screwed on tight. Remember to tighten the hexagon locking grub screw that fits 
into the end of the cover 

-

 

Ensure compliance with the words << DO NOT OPEN WHEN ENERGISED >>, 
clearly indicated on the cover. Alternatively, make the area safe before opening 
the sensor cover.

 

Electrical installation 
and configuration 

 
 

 

 
 

 
 

 

 

Terminal board and 
electrical connections 
 
 
 
 
 

 
 
 
 
 
 
 

Cabling:

 

 

CAUTION:  Make the area safe and ensure that the device power supply is off 
before cabling and configuration operations. 

Install the sensor in compliance with EN 60079-14. 
ATEX  certified  1“  NPT  cable  glands  are  used  for  cable  entry,  in  compliance  with 
standards EN 60079-0 and EN 60079-1 (Ex d protection mode). 
Ground the sensor using the internal grounding system. 
Refer  to  the  Control  Unit  manual  for  all  cabling  information  (cable  type  and 
specifications, bus topology, length of connections etc.) and configuration. 

 

 

 

 

 

 

 

 

 

 
 
 
 
 
 

Depending  on  the  connecting  distance,  use  at  least  4-core  cable,  min.  diameter 
0.75mm

2

 up to 100m, 1mm

2

 up to 200m, 1.5mm

2

 up to 500m. 

 
Use shielded cable where there is a risk of electromagnetic interference. 

12 Vdc power supply 
input

 

BUS input

 

BUS 
Shield

 

-

 

+

 

-

 

+

 

BUS

 

12V

 

Grounding 
connection 

Termination 
jumper 

Configuration key 

Cable connection 

Status LED 

Sensing element 

Power supply  
and BUS  
connector  