background image

 

Pag. 2/4 

E191.604_En   Rev. 4   dated 30/11/2018 

EsiWelma

®

 s.r.l.

 

Jumper Setup 

 

Set jumper JP2 

VALVE TYPE 

to NC for normally closed valve type 

(deliver condition) or to NO for normally open valve type. 

 

Set jumper JP3 

VALVE MODE

 only if normally open valve is used. 

C

ONT 

position  allows

 

to  set  EV  output  constantly  powered  in 

case of gas alarm, while 

PULSE 

position

 

allows

 

to set it powered 

by impulses at 10s intervals. 

  

Jumper for valve

mode selection

Jumper for valve 

type selection

VALVE / TYPE

     

NC

  

NO

VALVE / MODE

CONT.

 

PULSE

N

OTE: EACH  CHANGE  OF  JUMPER SETUP  MUST  BE  MADE  UNDER  POWER  OFF.

 

Button functions

 

 

O

UTPUT 

T

EST 

button:

 

if  pressed  for  at  least  5s,  starting  from 

normal  operating  condition,  temporarily  activates  all  outputs 
(valve  +  relay  +  hooter)  in  order  to  check  regular  operation  of 
intervention and signal devices. 

 

LED
TEST

RESET

OUTPUT
TEST

5s

 

  

E    V

C  NC NO

M

Relay outputs 
de-energized

EV outputs 
voltage absence (valve NC)
voltage presence (valve NO)

C  NC NO

Alarm

Fail

E    V

M

 

 Note: relay operation in positive logic  
  Energized relay = alarm / fault absence 
  De- energized relay = alarm / fault presence 

 

L

ED 

T

EST

 button: temporarily turns all LEDs ON in order to 

check their integrity. 

LED
TEST

RESET

OUTPUT
TEST

 

When button is 
released the 
LEDs go back to 
their status 
before the button 
was pressed 

Operation 

When  the  UCE18  is powered  at  24VAC 

preheating phase

  starts  up 

(about 1 min) while LEDs will indicate: 

 

Green LED flashing (frequency 1Hz) 

 

Control Unit Yellow LED steady on 

 

Sensor Yellow LEDs steady on 

 

Red LEDs steady on 

During  this  phase  there  is  no  voltage  at  EV  terminals,  so  it  is  not 
possible  to  energize  the  solenoid  valve(s)  if  NC  type,  while  it  is 
possible  to  energize  it/them  if  NO  type.  Further,  the  relays  are  not 
energized. 
After  preheating  phase,  the 

test  phase

  follows  (3  min)  while  it  is 

possible  to  check  sensors  operation.  To  this  purpose,  all  internal 
timings for alarm management are zeroed. 
In this phase LEDs will indicate: 

 

Green LED flashing (frequency 2Hz) 

 

Control Unit yellow LED steady on 

 

Sensors Yellow LEDs steady on 

 

Red LEDs steady on 

During  this  phase  there  is  voltage  at  NC  solenoid  valve(s),  so  it  is 
possible to open it/them using its manual actuator placed on the same 
valve. The relays are energized. 
Connect the battery to relevant terminals paying attention to polarity. 

Operation test 

During normal operation it is possible to simulate an alarm, in order to 
check system functionality. Act as follows: 

 

Activate  test  phase (if no more active after preheating) holding 
down RESET button for at least 5s. 

 

With  cover  fitted  on  approach  a  gas  source  to  a  sensor  grid, 
and let come out a small amount of gas. 

 

 

CAUTION:

 don’t spray the gas directly on the sensor, 

otherwise  it  will  be  permanently  damaged.  Act  to 
increase  gradually  the  gas  concentration  close  to  the 
sensing element. 
Sensors  can  be  permanently  damaged  when  exposed 
to  high  or  continuous  concentrations  of  interfering 
substances  (like  fresh  paint,  ammonia  based  cleaning 
materials, alcoholic or silicone solvents etc). 

To check carbon monoxide sensor a combustion smoke can be 
used. 

 
After these operation the control unit must indicate a gas alarm status 
with these effects: 

 

-

  Sensor Red LED flashing 

-

  Solenoid valve(s) driven to 

closed position 

-

  Changeover of alarm relay 

contact (closed contact C -NC) 

-

  Piezoelectric hooter activated       

(if present) 

 

To restore normal operation, once alarm status is over, press RESET. 
 

1

2

3

4

LED
TEST

RESET

OUTPUT
TEST

 

-

  Sensor Red LED re-

verts to steady on 

-

  Alarm relay contact 

reverts to initial position 
(closed contact C - NO) 

-

  Piezoelectric hooter 

deactivated (if present) 

 

 

Note:  

 

An  alarm  or  fault  condition  during  test  phase  (3  min)  causes 
flashing  of  the  relevant  red  or  yellow  LEDs  at  2Hz  frequency 
instead of 1Hz as indicated in functional table. This latter will be 
valid for events starting from normal operating condition. 

 

Return to normal operating condition by pressing RESET button 
is possible only if there aren’t any active alarms. 

Open the solenoid valve(s) manually. 
 

The  control  unit continuously checks  connections  integrity  both 
for sensors and valves. 
 

The sensor will perform best if used in an area where the 
only gas or vapor present, besides fresh air, is the gas or 
vapor that you wish to detect. 

If  used in  an  area  contaminated with relative high concentration 
of  different  interfering  substances  (like  fresh  paint,  ammonia 
based  cleaning  materials,  alcoholic  or  silicone  solvents  etc.), 
false alarms may occur. 

         IMPORTANT

 

We  recommend  to  repeat  operating  test  at  least  once  a  year  or 
after a long stop period and in any case every time that a sensor 
is replaced. 

Reviews: