esera automation Multisensor Pro I User Manual Download Page 5

 

 
 

Art. No. 11151  

 

 

 

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of 
ESERA GmbH. Errors and technical modification subject to change. 



ESERA GmbH, ESERA-Automation 2020 

www.esera.de 

11151 V2.0 R1.0  Manual 

Page 5 of 8 

Calculations 
Temperature 

Standard output according to DS2438 module 
 

Operating voltage 

Standard output according to DS2438 module 
 

Humidity 

To obtain the rel. humidity in percent, multiply the output value (Vas) by a factor of 10. 0.1V corresponds to 
1% relative humidity. 

 
Air quality 

Air quality is output on the basis of (equivalent) CO2 sensors. 
After starting the sensor the first time, it will output 0V for a few minutes. This means that the air quality 
sensor has switched in start up mode. 
In normal operation, the minimum output value is 30.5mV, which equals 405 ppm equivalent CO2. 
An increase of the output voltage is in the ratio 1mV per 11.6ppm CO2. 
As an example, an output voltage of 60.2mV corresponds to 698.3ppm CO2. 
 

12 

Data output 1-Wire Controller / 1-Wire Gateway 

For the 1-Wire Multisensor Pro I, the following measured values are output by the 1-Wire Controller / 1-Wire 
Gateway.  
 

Data output:  

1_EVT|12:27:40 
1_OWD1_1|2008   => controller no._module no._data record | temperature (°C) example: 20,08 °C  
1_OWD1_2|511     => controller no._module no._data record |voltage VCC (V)  
1_OWD1_3|850     => controller no._module no._data record |rel. humidity (rF) example 85,0%  
1_OWD1_4|1200   => controller no._module no._data record |dew point (°C) example: 12,00 °C 
1_OWD1_4|80000 => controller no._module no._data record |air quality (ppm CO2) example: 800,00 ppm 
 
Further information for options and commands can be found in the latest available documentation for 1

–Wire 

Controller / 1

–Wire Gateway. 

 

13 

Integration in IP-Symcon / ESERA-Station 

Through our website we provide ESERA IP-Symcon software-modules to import the 1-Wire Multisensor in 
IP-Symcon via 1-Wire Controller / 1-Wire Gateway. Therefore, no scripts are necessary.  
Further details can be found here: 

https://www.esera.de/kompatible-steuerungen-zentralen/ip-symcon-

integration/

 

 
For a conventional connection by a 1-wire bus coupler, the sensor values are to be calculated according to 
the given formulas. 
 

14 

Integration in Loxone 

At our webshop we provide a sample project on how to import the 1-wire Multisensor by 1-Wire Controller 
1/1-Wire Gateway.  
Further details can be found here: 

https://www.esera.de/kompatible-steuerungen-zentralen/loxone-

integration/demo-1-wire-controller-1-loxone-integration/ 

 

15 

Integration in FHEM 

For integration into the open source automation software FHEM, we provide a software module to import in 
the 1-wire Multisensor by 1-wire controller / 1-wire gateway. Therefore, no scripts are necessary. 
Further details can be found here: 

https://www.esera.de/kompatible-steuerungen-zentralen/fhem-integration/

 

 
 

Summary of Contents for Multisensor Pro I

Page 1: ...red a professional and highly accurate multi sensor Due to the new technology of the ESERA 1 Wire Pro sensors the accuracy of humidity measurements is on average 200 300 higher compared to most standard sensors on the market In addition the evaluation of the delivered measured values is enormously simplified The 1 Wire Multisensor Pro enables simple climate monitoring of all rooms and buildings Th...

Page 2: ...zes ESERA chips sensors and actuators starts suitable libraries and outputs fully formatted data The Auto E Connect functionality will be available from mid 2020 via 1 Wire Controllers 1 Wire Gateways and 1 Wire ECO from ESERA available Further information on ESERA Auto E Connect can be found on the ESERA website ESERA Config Tool 3 or in the download area for this article in the ESERA Webshop 4 T...

Page 3: ... the LED display may be permanently off Table 7 1 8 Commissioning and warm up A calibration of the temperature and humidity sensor is not necessary The air quality sensor is pre calibrated After applying the supply voltage the integrated sensor controller checks the warm up time after which the air quality sensor starts The three possible stages of the warm up phases are indicated by the three LED...

Page 4: ...hat the calibration process will start shortly During the calibration process the red LED flashes rapidly After the calibration has been completed the sensor automatically switches to normal operation The sensor is very sensitive and already reacts to the presence of people so stay away from the sensor during calibration Due to the system the air quality sensor is subject to low aging which is com...

Page 5: ...r no _module no _data record voltage VCC V 1_OWD1_3 850 controller no _module no _data record rel humidity rF example 85 0 1_OWD1_4 1200 controller no _module no _data record dew point C example 12 00 C 1_OWD1_4 80000 controller no _module no _data record air quality ppm CO2 example 800 00 ppm Further information for options and commands can be found in the latest available documentation for 1 Wir...

Page 6: ... 8 1 Wire networks can be set up in star or tree cabling of approx 30 80m in total We recommend the use of CAT 5 7 network cables for the installation You will find a recommendation for cable assignment in the download section of this article Shielded cable e g CAT5 or CAT6 cable should be used in smart homes commercial buildings and industrial environments This ensures very good system stability ...

Page 7: ...During installation and handling of components which later have mains potential on their parts the relevant VDE regulations must be observed Devices that are to be operated at a voltage greater than 35 VDC 12mA may only be connected by a qualified electrician and put into operation Commissioning may only be realized if the circuit is built into a contact proof housing If measurements with an open ...

Page 8: ...0 www esera de 11151 V2 0 R1 0 Manual Page 8 of 8 Moreover from their appearance on ESERA GmbH webpages it cannot be concluded that designations logos names and trademarks are free of commercial property rights ESERA and Auto E Connect are registered trademarks of ESERA GmbH 25 Contact ESERA GmbH Adelindastrasse 20 87600 Kaufbeuren GERMANY Tel 49 8341 999 80 0 Fax 49 8341 999 80 10 www esera de in...