background image

All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of 
ESERA GmbH. Errors and technical modification subject to change. 



ESERA GmbH, ESERA-Automation 2020 

www.esera.de 

11150 V2.0 R1.0  Manual 

Page 2 of 5 

 
 

Auto-E-Connect® Support 

The ESERA 

Auto-E-Connect®

 1-Wire Plug and Play system will be used for the  

1-Wire Bus supported. This enables fully automatic configurations of 1-Wire sensors 
and actuators on the 1-Wire bus. It is optimized for industrial applications and 
enables significant added value beyond the sensor and chip data. 
The Auto-E-Connect function automatically recognizes ESERA chips, sensors and actuators, starts suitable 
libraries and outputs fully formatted data. 
The Auto-E-Connect functionality will be available from mid-2020 via 1-Wire Controllers, 1-Wire Gateways and  
1-Wire ECO from ESERA available. 
Further information on ESERA Auto-E-Connect can be found on the ESERA website, ESERA Config-Tool 3, or in 
the download area for this article in the ESERA Webshop. 
 

Technical data 

Function:  

Multisensor for temperature and rel. humidity and air quality, 

 

monitoring of operating voltage 

Temperature sensor: 

Precise digital temperature sensor with 12 Bit measurement resolution 

Range of measuring temp.:   -40°C to +60°C (sensor element: -40°C to +85°C) 
Accuracy temperature: 

0,3° in the range of -10°C - 60°C (more accurate than the DS18B20 sensor) 

Resolution: 

12 Bit, 0,06°C/Bit depending on selected resolution 

 
Humidity sensor: 

Capacitive digital humidity sensor with high accuracy 

Range of measuring hum.:  0-100% rel. humidity 
Accuracy humidity: 

+/-3 % in the range of 10-85% rel. humidity 

Data output: 

0-10V equates 0-100% rel. humidity, 0,1V = 1% rF 

 
Interface: 

3 - wire connection (data, ground and 5V, parasitic operation not supported) 

Connection: 

Push-in clamps for cable solid 0,2 to 2,5qmm or finely stranded 0.2 to 1,5qmm 
For connection we recommend slotted screwdriver of the size 2,5x751-Wire 
interface 

 

1-Wire interface:  

      Basis DS2438 

Operating voltage: 

5 V= (+10% / -20%) 

Current consumption: 

approx. 2 mA 

 

Ambient conditions

 

Protection system: 

IP20 

Protection class: 

III 

Temperature, operation:  -25°C to 70°C, (limitation by carrier system, sensor -40°C to +125°C) 
Humidity: 

 

10 - 90% (non condensing) 

Outer dimensions: 

71 x 71 x 32mm (LxWxH) 

 

Conformity 

EN 50090-2-2 
EN 61000-4-2, ESD 
EN 61000-4-3, HF 
EN 61000-4-4, Burst 
EN 61000-4-5, Surge 
EN 61000-6-1, interference immunity 
EN 61000-6-3, interference radiation 
RoHS 
 

Software / Control 

The 1-Wire Multisensor Pro is being read out per 1-Wire commands for the DS2438 modules. The sensor is 
supported by many systems such as ESERA Station, Loxone, IP-Symcon, OWFS, FHEM (Linux) or 
microcontroller applications. 
 
For ESERA 1-Wire Multisensors of the Pro series no elaborate formulas are necessary. 
A sensor controller within the Multisensor takes over the preprocessing of all measured values and thereby 
enormously simplifies the integration into 1-wire systems. The measured values are no longer dependent on 
the operating voltage of a 1-Wire Multisensor. 
 

 

The values measured by the sensor are assigned to the standard DS2438 module values as follows: 
VDD = operating voltage (5V), TEMP = temperature, VAD = humidity, Xsense = no data output, fixed at 0. 

Summary of Contents for Multisensor Pro 11150

Page 1: ... on the market Due to the use of highly integrated sensors with 12 bit resolution the 1 Wire Multisensor delivers very accurate values for temperature and relative humidity In addition the evaluation of the delivered measured values is enormously simplified The 1 Wire Multisensor Pro enables easy climate monitoring of all rooms and buildings The 1 Wire Multisensor Pro is installed in a stylish wal...

Page 2: ...apacitive digital humidity sensor with high accuracy Range of measuring hum 0 100 rel humidity Accuracy humidity 3 in the range of 10 85 rel humidity Data output 0 10V equates 0 100 rel humidity 0 1V 1 rF Interface 3 wire connection data ground and 5V parasitic operation not supported Connection Push in clamps for cable solid 0 2 to 2 5qmm or finely stranded 0 2 to 1 5qmm For connection we recomme...

Page 3: ...found in the latest available documentation for 1 Wire Controller 1 Wire Gateway 9 Integration in IP Symcon ESERA Station Through our website we provide ESERA IP Symcon software modules to import the 1 Wire Multisensor in IP Symcon via 1 Wire Controller 1 Wire Gateway Therefore no scripts are necessary Further details can be found here https www esera de kompatible steuerungen zentralen ip symcon ...

Page 4: ...re advantage of cabling with CAT cable is that a linear bus topology can be achieved despite star shaped cable routing in buildings This is only possible with the 8 core cable construction of a CAT cable We recommend a linear topology When using CAT7 cables the maximum possible cable length of the entire 1 Wire network is reduced due to the stronger shielding and the resulting higher cable capacit...

Page 5: ...ests according to DGUV regulation 3 German statutory accident insurance https en wikipedia org wiki German_Statutory_Accident_Insurance must be carried out 19 Warranty ESERA GmbH guarantees that the goods sold at the time of transfer of risk to be free from material and workmanship defects and have the contractually assured characteristics The statutory warranty period of two years begins from dat...

Reviews: