Technical data
Ethernet interface:
- TCP/IP, Socket Server
- 10/100 MBit/s Ethernet Interface, WLAN: 802.11 b/g, LAN 10/100MBit/s
- up to 20 data connections for ModbusTCP
- Auto Negotiation (Full-duplex and Half-duplex)
- Auto MDI/MDIX
- Support for DHCP and fixed IP-Adress
Auto-E-Connect:
Level I to III supported
Data, Firmware Update
and Configuration
ESERA Config Tool 3
Software Support:
ECO Dashboard 100
Supply voltage: -38VDC to -72VDC
Current consumption
max. 100mA
Power supply RTC:
Goldcap, buffering of the internal clock (RTC) in case of power failure for approx. 2 days.
In the event of a longer failure, the RTC must be reset.
The Goldcap is charged after approx. 2 hours.
1-Wire Interface :
1-Wire Bus (+5V, ground (GND) and data)
Protective circuits:
ESD, overvoltage and reverse polarity protection.
Connection:
Push In plug-in terminals (up to 2.5qmm cable cross-section)
Output voltage:
+5V (+/-10%), max. 300mA, overload, overvoltage and short-circuit proof
Isolation:
Galvanic isolation between Ethernet and 1-Wire Interface
Supported
DS2401, DS1963, DS1990, DS1820, DS18S20, DS18B20, DS2413, DS2438, DS2450
1-Wire devices:
DS2408, DS2405, DS2406 (only input), DS2423, other chips on request.
We will be happy to support other components as an OEM product for you.
5
Ambient conditons
Temperature, operation: -25°C to +60°C
Storage temperature: -20°C to +70°C
Relative air humidity:
10% to 92% (non condensing)
Room classification: operate only in dry rooms
Protection system:
IP20
Protection class:
III
Dimensions:
106,3 x 90,5 x 62mm (WxHxD)
6
Conformity
EN 50090-2-2
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, interference immunity
EN 61000-6-3, interference radiation
RoHS
7
Display LED
The module has various indicator LEDs. The function of the indicators is as follows
Display
Designation
Function
LED Green
PWR
Display for supply voltage
LED Green
DATA
after switching on the unit, the LED flashes 3x
flashes during 1-Wire activity
flashes when data is sent via the data interface
flashes very quickly if "KAL Receive" has been
activated and the "KAL Messages" of the control
system are missing.
LED Green
LAN
LAN - Network Status LED
lights up when LAN - Network connection is established
flashes when the interface is not activated