5.3. Central heating circuit circulating pump with an external alarm control system.

Functions performed by the controller in the system: 
–central heating circulating pump control 
–external acoustic signaller control
–system protection against overheating

Tips for parameters programming: 
F10=0 (T1 pipeline temperature measurement) 
F11=pump start temperature setting, for example 40 °C 
F12=pump switching hysteresis, for example 0.1 °C
F15=high temperature alarm in boiler, for example 85 °C
F16=OFF; F1 = 0.1; F21 = 0 
F29=COOLING (switching pump after reaching the 
temperature of the boiler) 
F50=0 or 2 (2 – if you used an external safety thermostat 
STB connected to the D1 input) 
F51=1 (sound signaller active) 
F52=0 (when the high temperature alarm occurs, the 
pump switches on to cool down the water in the boiler) 

Auxiliary 
output

Time

0

1

85°C

T1

Boiler

Alarm

Central
heating
pump

40°C

F15

Cold water

5.4. Domestic hot water circuit circulating pump with an external alarm control system.

T1

Alarm

D.h.w. Pump 

F15

F11±F12

Main

output

Time

Time

Temp.

0

1

Functions performed by the controller in the system: 
–domestic hot water circulating pump control
–external acoustic signaller control
–system protection from overheating  

Tips for parameters programming: 
F10 = 0 (T1 boiler temperature measurement) 
F11 = boiler temperature setting, for example 60 °C
F12 = pump switching hysteresis, for example 0.1 °C 
F15 = high temperature alarm, for example 85 °C 
F16 = OFF; F17 = 0.1; F21 = 0 
F29 = HEATING (pump works until the temperature is 
reached) 
F50 = 0 or 2 (2 – if you used an external safety thermostat 
STB connected to the D1 input) 
F51 = 1 (sound signaller active) 
F52 = 1 (when high temperature alarm occurs, the pumps 
is switched on) 

Auxiliary 
output

85°C

60°C

Time

0

1

Boiler

5.5. Solar collector with an external alarm control system .

T1

Cp

T2

Alarm

F12=2

°C

F12=2

°C

6°C

8°C

Main 

output

Time

Time

0

1

10°C

Functions performed by the controller in the system: 
–collector pump control
–external acoustic signaller control
–boiler protection against overheating 
Tips for parameters programming: 
F10=1 (boiler T1 and collector T2 temperature 
measurement) 
F11=temperature difference T2-T1 between the solar 
collector and the boiler after reaching 
that, the collector's pump switches on, for example 8 °C 
F12=pump switching hysteresis, for example 2 °C 
F15=boiler overheating alarm, for example 85 °C 
F16=OFF; F17 = 0.1; F21 = 0, F29 = COOL; F50 = 0
F51=1 (sound signaller active) 
F52=0 (when the boiler overheating alarm occurs, pump is 
turned off so as not to collect a hot factor from the 
collector) 

Auxiliary 
output

Time

0

1

T2-T1

When T1>F15

F11

5.6. Fireplace with water jacket control system.

Functions performed by the controller in the system: 
- fireplace pump control 
- central heating circulating pump control.
Tips for parameters programming: 
F10=1 (boiler T1 and fireplace T2 temp. measurement)
F11=setting specifying the fireplace temperature growth in 
relation to the boiler temperature so that the fireplace pump 
switches on, for example 8 °C
F12=fireplace pump switching hysteresis, for example 2 °C 
F15=set water temperature in the boiler. Loading the 
domestic hot water boiler using the fireplace pump is a 
priority, so that only after reaching this setting, the central 
heating pump switches on, for example 60 °C 
F16=OFF; F17=0.1; F21=0; F29=COOL; F50=0; F51=0 
F52 = 0 (when the central heating pump switches on, 
fireplace pump is switched off) 

F12=2

°C

F12=2

°C

6°C

8°C

F11

Main

output

Time

Time

Temp.

0

1

10°C

Auxiliary 
output

When T1<F16

Time

0

1

T2-T1

SC-20 

T1 - boiler temperature sensor
T2 - fireplace temperature sensor  
Collector pump and c.h. pump max. 400W 230V~

Power supply

230V~

20(8)A

8(2)A

T2

Pc

Pch

13 14 15 16

12

11

Temp

M

set

M

set

M

set

SC-20 

T1 - boiler temperature sensor
T2 - collector temperature sensor
Collector pump Pk and signaller max. 400W 230V~

Power supply

230V~

20(8)A

8(2)A

Alarm

T2

Pc

13 14 15 16

12

11

SC-20 

T1 - main temperature sensor
D1 - external safety thermostat STB 
Pompa Pdhw i signaller max. 400W 230V~

Power supply

230V~

20(8)A

8(2)A

Alarm

Thermostat

STB

Pdhw

13 14 15 16

12

11

SC-20 

T1 - main temperature sensor
D1 - external temperature sensor STB 
Pump Pch and signaller max. 400W 230V~

Power supply

230V~

20(8)A

8(2)A

Alarm

Thermostat

STB

Pch

13 14 15 16

12

11

Pch

Pc

Cold
Water

T2

FIREPLACE

T1

M

set