Here are some examples of control systems using the SC-20 including diagrams of supported 
installations, tips for programming and diagrams of electric connections. 

5.2. Heater with external alarm control system.

5.3. Heater and fan control system.

6. DIGITAL INPUT.

7. ALARM MESSAGES.

Controller  has  digital  input  D1  for  emergency  states  signalling,  such  as  system  failure, 
pressure  control  or  safety  thermostat  activation,  etc.  Input  type  (normally  opened,  normally 
closed) is programmed by F50 parameter. After opening/closing circuit of 4-5 digital input, the 
controller turns off the main output and turns on the sound signaller (beep)  and an auxiliary output 
and the display shows A11 code. Emergency state sound signalling can be maintained, until the 
alarm reset by using the buttons (F50=2 or 4). 

When alarm activates the indicator        starts to blink and the sound signaller (beep) activates 
(when F83=1). According to the occurence controller turns on/off output and the front panel 
displays one of the following alarm messages: 

8

Statement

Occurence

digital input activation F50 

T1 sensor error:
open circuit or short circuit 

Output operation 

auxiliary output active, the main inactive

auxiliary output active, the main inactive 

T2 sensor error:
open circuit or short circuit 

auxiliary output active, the main inactive  

high temperature alarm F15 

auxiliary output active, the main depends on 
the setting of F52 

low temperature alarm F16 

auxiliary output active, the main depends on 
the setting of F52 

T1+T2

2

5.7. Chamber, incubator and boiler with adjustment calculated from the arithmetic 
mean of the measurements from two temperature sensors T1 and T1 PRECISE 
control system. 

F12=1

°C

F12=1

°C

79°C

80°C

Main 

output

Time

Time

Temp.

0

1

81°C

Functions performed by the controller in the system:
–heater control
–external acoustic signaller control 
–system protection against overheating and freezing 
–emergency states sound signalling

Tips for parameters programming: 
F10 = 2 (temperature measurement from two sensors T1 
and T2)
F11 = temperature setting 
F12 = heater switching hysteresis, for example 1 °C 
F15 = high temperature alarm, for example 85 °C 
F16 = low temperature alarm, for example 5 °C 
F17 = 0.1; F21 = 0; 
F29 = HEATING; 
F50 = 0; F51 = 1; F52 =0 

Auxiliary 
output

1

85°C

5°C

F15

F11

F16

Time

0

F12=1

°C

F12=1

°C

79°C

80°C

Main

output

Time

Time

Temp.

0

1

81°C

Functions performed by the controller in the system: 
–heater control (boiler, electric heater, etc.)
–external acoustic signaller control
–system protection against overheating and freezing
–emergency states sound signalling 

Tips for parameters programming: 
F10 = 0 (system temp. measurement from T1 sensor)
F11 = temperature setting
F12 = heater switching hysteresis, for example 1 °C
F15 = high temperature alarm, for example 85 °C  
F16 = low temperature alarm, for example 5 °C 
F17 = 0.1; F21=0; F29=HEATING 
F50 = 0 or 2 (2 – if you used the external safety thermostat 
STB connected to the D1 input) 
F51 = 1 (sound signaller active) 
F52 = 0 (heater off in danger point) 

Auxiliary output

Time

0

1

85°C

5°C

F15

F11

F16

F12=1

°C

F12=1

°C

19°C

20°C

Main

output

Time

czas

Temp.

0

1

21°C

Functions performed by the controller in the system: 
–heater heating up the chamber control
–fan cooling the chamber control
–emergency states sound signalling 

Tips for parameters programming: 
F10 = 0 (temperature measurement from T1 sensor)
F11 = temperature setting
F12 = heater switching hysteresis, for example 1 °C
F15 = temperature setting of switching the fan cooling the 
chamber, for example 30 °C
F16 = OFF
F17 = 0.1; F21 = 0 
F29 = HEATING 
F50 = 0 or 2 (2 – if you used the external safety thermostat 
STB connected to the D1 input) 
F51 = 0; F52 = 0 

Auxiliary output

1

30°C

F15

F11

Time

0

SC-20 

T1 - boiler temperature sensor
T2 - fireplace temperature sensor 
Heater max. 3200W, Signaller 230V~

Power supply

230V~

20(8)A

8(2)A

T2

Electr.
Heater

Alarm

13 14 15 16

12

11

Alarm

Heater

SC-20 

T1 - main temperature sensor
D1 - external safety thermostat STB 
Heater max. 3200W, signaller 230V~

Power supply

230V~

20(8)A

8(2)A

Thermostat

STB

13 14 15 16

12

11

Wentylator

Grzałka

SC-20 

T1 - main temperature sensor
D1 - external safety thermostat STB 
Heater max. 3200W, fan 400W 230V~

Power supply

230V~

20(8)A

8(2)A

Termostat

STB

13 14 15 16

12

11

BOILER

T1

T2

Heater

~

2

3

0

V

Alarm

M

set

T1

Alarm

Heater

M

set

T1

      Fan

Heater

M

set