INSTALLATION 3-2 Manual 0-5458
Figure 3-1: Electrical Input Connections
!
CAUTION
The time-delay fuses or circuit breaker of an individual branch circuit may have nuisance tripping when
welding with this product due to the amperage rating of the time-delay fuses or circuit breaker.
The recommended time-delay fuses or circuit breaker size is 20 amperes. Fuse/circuit breaker size is
based on not more than 200 percent of the rated input amperage of the welding power source (Based on
Article 630, National Electrical Code).
An individual branch circuit capable of carrying 20 amperes and time-delay fuses or circuit breaker protec-
tion is recommended for this application.
Art #: A-08473_AB
Welding Power Supply
Primary Power Cable
120 V, 20A, 1Ø
Refer to Figure 3-1:
1. Connect end of ground (GREEN or GREEN/YELLOW) conductor to a suitable ground. Use a grounding method that complies
with all applicable electrical codes.
2. Connect ends of line 1 (BLACK) and line 2 (WHITE) input conductors to a de-energized line disconnect switch.
3. Use Table 3-1 as a guide to select line fuses for the disconnect switch.
Input Voltage
Fuse Size
115V
20 Amps
Table 3-1: Fuse Guide