6.2.
Programming level for configuration P-00
Param.
Description
Range
Default
Value
0-00
Input range
0 -> Thermocouple type K
-100 to +1370 °C
1 -> Thermocouple type J
-100 to +1000 °C
2 -> Thermocouple type S
0 to +1750 °C
3 -> Thermocouple type L
-100 to +900 °C
4 -> Thermocouple type R
0 to 1590 °C
5 -> RTD (Pt100) 2/3-Wire
-200 to +800 °C
6 -> Voltage 0 - 2 V
7 -> Voltage 0 - 200 mV
0 .. 7
0
0-01
Display value of min. input signal
for input ranges 6 and 7
-999 .. +9999
0
0-02
Display value of max. input signal
for input ranges 6 and 7
-999 .. +9999
+2000
0-03
Programmable points
0 ->
XXXX
1 ->
XXX.X
2 ->
XX.XX
3 ->
X.XXX
0 .. 3
0
0-04
Configuration of digit 1
0 ->
Display in steps of 1
1 ->
Display in steps of 2
2 ->
Display in steps of 5
3 ->
Display in steps of 10
0 .. 3
0
0-05
Filtering
0 ->
no filtering
X ->
Number of filter cycles
0 .. 99
0
0-06
Resolution
0 ->
Resolution 1 °C
1 ->
Resolution 0,1 °C
only for input ranges 1/3/5
0 .. 1
0
0-07
Cold junction
0 ->
Only thermocouple
1 ->
Thermo internal
cold junction
2 ->
Temperature of the internal
temperature sensor
0 .. 2
0