4 Protection Functions and Specifications
4-40
L-PRO 4000 User Manual
D02706R02.30
50N/51N/67
Neutral
Overcurrent
Neutral overcurrent provides backup protection for line to ground faults. The
user can define directional or non directional control on either 50N or 51N
functions. 51N can also be configured for use in the communication scheme.
All the curve definitions are the same as the phase overcurrent except that this
function uses 3I0 rather than phase current. The equation is:
For 3
I0
> pickup
(7)
For 3
I0
< pickup
(8)
Table 4.23: 50N/51N/67 Neutral Overcurrent Settings
50N
Enable/Disable
Directional
Directional, non-directional, combined
Pickup (3I
0
)
0.25 to 50.00 (5 A)
0.05 to 10.00 (1 A)
Pickup Delay
0.00 to 99.99 seconds non-directional
0.01 to 99.99 seconds directional
51N
Enable/Disable
Directional
Directional, non-directional, combined or direction in scheme
Pickup (3I
0
)
0.25 to 50.00 (5 A)
0.05 to 10.00 (1 A)
Curve Type
For details see Table 4.21: IEC and IEEE Curves on page 38.
TMS
0.01 to 10.00
A
0.0010 to 1000.0000
B
0.0000 to 10.0000
p
0.01 to 10.00
TR
0.10 to 100.00
Directional Angle Setting
Alpha
-179.90 to 180.00
Beta
0.10 to 360.00
T
3
I
0
TMS B
A
3
I
0
Pickup
------------------
p
1
–
------------------------------------
+
=
T
3
I
0
TMS
TR
3
IO
Pickup
------------------
2
1
–
-----------------------------------
=
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......