2400VS SERIES
Erie Water Treatment Controls – Belgium
Page 11
Programming instructions - Parameter Set level
In the Parameter Set level the basic configuration parameters of the unit can be programmed, depending on the
specific configuration of the unit.
Before entering the programming mode, make sure that the control valve is in the service mode.
1.
Press the
scroll
button and hold it for 5 sec until the display shows:
2.
Within 10 sec, press the
up
button; the display will show:
Press the
up
button or
down
button to set
the units of hardness
.
3.
Press the
scroll
button again; the display will show:
Press the
up
button or
down
button to set
the exchange capacity per litre of resin
.
4.
Press the
scroll
button again; the display will show:
Press the
up
button or
down
button to set
the volume of resin
.
5.
Press the
scroll
button again; the display will show:
Press the
up
button or
down
button to set
the number of days between regenerations
.
6.
Press the
scroll
button again; the display will show:
Press the
up
button or
down
button to set
the length of the regeneration cycle
.
Default setting
Setting range
Cycle 1
Backwash
5 min
0-20 min
Cycle 2
Brine draw/slow rinse
60 min
0-180 min
Cycle 3
Fast rinse/refill
5 min
0-65 min
7.
Press the
scroll
button again; the display will show:
Press the
up
button or
down
button to set
the model of flow meter used
:
-
SNAP SENSOR
: model with snap-on flow meter sensor.
-
SCREW SENSOR
: model with sensor fixed by means of screw.
System Check
Cycle 1: 5 min
HardUnit:°f
ExCap:5.2°f M3/L
Resin: 20 liters
Override: 4 days
MTR:SNAP SENSOR
5: XX min
Summary of Contents for 2400VS Series
Page 1: ...A Division of Aquion Inc 2400VS SERIES Technical Manual...
Page 3: ...A Division of Aquion Inc Art Nr Tech_Man ENG 2400VS 2013 06...
Page 4: ......
Page 23: ...2400VS SERIES Erie Water Treatment Controls Belgium Page 19...
Page 30: ...2400VS SERIES Erie Water Treatment Controls Belgium Page 26 Valve body...
Page 33: ......