2400TS SERIES
Erie Water Treatment Controls – Belgium
Page 12
Diagnostics level
Besides of all programming parameters, a series of operating parameters can be consulted in the diagnostics level;
particularly during a service intervention, these parameters can be helpful to identify the cause of a problem.
1.
Accessing the Diagnostics level:
Make sure that the control valve is in the service mode.
Push the
scroll
button and hold it for 5 sec until the display shows:
Within 10 sec, push the
down
button; the display will show:
You are now in the Diagnostics level; use the
scroll
button to advance through the different diagnostics
parameters.
2.
Exiting the Diagnostics level:
If no button is pushed within a time frame of 5 minutes, the microprocessor will exit the diagnostics level
end return to the service mode.
Push the
scroll
button until the display shows:
Push the
up
button or
down
button to exit the Diagnostics level.
3.
Available diagnostic parameters:
In Srvc
: displays show many days the unit has been in service.
# of Regens
: display shows the number of regenerations that have taken place since installation.
MP Resets
: display shows the number of resets of the microprocessor (
for factory purpose only
).
Memory Reset
: display shows the number of corrupt memory start-ups (
for factory purpose only
).
EZ
: display shows the software version (
for factory purpose only
).
System Check
Exit
In Srvc Xdays
Summary of Contents for 2400TS Series
Page 1: ... A Division of Aquion Inc 2400TS SERIES Technical Manual ...
Page 15: ...2400TS SERIES Erie Water Treatment Controls Belgium Page 13 ...
Page 21: ...2400TS SERIES Erie Water Treatment Controls Belgium Page 19 ...
Page 28: ...2400TS SERIES Erie Water Treatment Controls Belgium Page 26 Valve body ...
Page 31: ......