Install lugs and spacers. Crimp lugs and wires together

prior to install. Apply anti-oxide compound to both 

sides of each lug.

Spacer

Lug

Maximum Lug Size: 6 AWG, two-hole lugs

Install outer hardware. Do not tighten.

3/8 Flat Washer

Belleville Washer

3/8-16 Hex Nut

3/8-16 Acorn Nut

Tighten connector bolt.

Apply 12 ft-lbs (max)

Note: In the absence of a torque wrench, snug bolt 

and tighten 1/4-turn.

Tighten inner and outer hardware. 

Apply torque as shown.

Hold

Note: In the absence of a torque wrench, snug bolt 

and tighten 1/4-turn.

Apply 20 ft-lbs (max)

The grounding bus must be electrically connected to the grounding system. Down-conductors may be used to 

connect the grounding bus to the grounding system (6 AWG or larger). When using a CADWELD® exothermic 

connection to connect the structure to the grounding system, remove the galvanized coating prior to welding. 

After installation or welding, cover exposed steel with cold galvanized coating (T372A, T358 or equivalent) if 

attached to a galvanized steel structure.

TECHNICAL SUPPORT

www.erico.com

IP8250_B

2 OF 2