It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the 

requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection 

of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior 

to full testing and power-up. Any other regulations applicable to the equipment being installed such as the 

Machinery Directive and current health and safety legislation must also be adhered to.  

All connections (including factory made) must be checked for the correct tightness prior to commissioning of 

the electrical installation.

All connections should be checked periodically to ensure correct tightness.

Important Safety Notice

DO NOT USE POWER TOOLS ON THESE PRODUCTS

!

SPD Specification

Technical Data

: Safe Surge Unit | ECSS-102

TY6 30N

According the IEC61643-11

Type 2

Earthing System

TT/TN

System Voltage

Un

230/400V

Max. continous operation AC voltage

Uc

275V

Norminal discharge current (8/20µs)

In

15kA

Maximum discharge current (8/20µs)

Imax

30kA

Voltage protection level 

Up

1.5kV

Maximum backup fuse 

63A gL

Response time

tA

25ns

Enviroment temperature

Tu

-40 ̊C ~ 80 ̊C

Status indicator 

non/red

Mounting

35mm Din Rail

Cross section of wire (min.)

4mm

Cross section of wire (max.)

16mm

Casing material

Thermal plastic 

UL94 - V0

Degree of protection

IP20

Enclosure Dimensions

MCB Specification

Product Ranges

EUC1P, EUC2P, EUC3P

Standard (s)

IEC 60898, EN 60898

Certification

KEMA

Characteristic Curves

B, C & D

Rated Current (In)

1, 2, 4, 6, 10, 16, 20, 25, 32, 40, 50 & 63A

Rated Voltage (Ue)

AC 230(240)/400(415)V

Rated Frequency

50/60Hz

Rated impulse withstand voltage (Uimp)

4kV

Energy Limiting Class

3

Number of poles

1, 2 & 3

Rated Short-Circuit Capacity (Icn)

10Ka

Operating Temperature

-5

̊ 

to 40

 ̊

C*

Altitude

Not exceeding 2000 metres 

Humidity

Not exceeding 50% at 40 

̊

C and 90% at 20

 ̊

C

Pollution Degree

2

Overvoltage Category

III

Terminal Protection

IP20

Mounting

35mm DIN Rail

Terminal Type

Tunnel

Terminal Capacity

1.0-25mm²

Recommended Terminal Torque

2.0Nm

* average not exceeding 35 

̊

C over 24 hour period

238

105

78

102

32 DIA.

181

55

6 DIA.