below to configure the DL6000-MEDH+. A new window should appear with the
following menu in the text box.
BIOS MANAGER for DL6000-1.00- Jun 16,06
(c) Equustek Solutions Inc. 2006
MAIN MENU
1 - Restore EEPROM
2 - WRITE new Firmware
3 - Memory DUMP
4 - OFF-LINE Diagnostics
5 - DEBUG Mode
6 - FIRMWARE Version
7 – ONLINE
8 - CONFIGURE Model Parameters
MAKE SELECTION (1-8) -
1.
Press 8 to configure the Modbus Parameters. The following will appear.
Enter Modbus Translation table parameters for Modicon to AB mapping.
AT Any time hit <ENTER> To Keep existing parameter value
Hit <ENTER> To continue, <ESC> to exit
2.
Press Enter to continue. You will then be asked to select a PLC type that the DL6000
will be communicating to.
Select A-B PLC TYPE: SLC/Micrologix
Enter 0 for PLC5, 1 for PLC3 or 2 for SLC or Micrologix or <ENTER> to keep:
3.
After selecting the PLC type you will then be asked to enter the values for the
translation table. Leading zeros need to be entered when using the DL Offline
Manager to configure the DL6000. After entering the translation parameters, press
Enter to proceed to the end of the table.
Program Modbus/A-B Translation Parameters
Hit <ENTER> to keep exsiting value or Type in New Value
Need to enter Leading Zeros. IE. file 7 = 007
Hit <ENTER> to Proceed any other key to exit now.
REC No Modbus Start Add. Modbus End Add. A-B Start Address Floating Point
(File:Word)
xxxxx xxxxx xxx:xxx Yes/No
00 40001 40010 007:000 N
01 30001 30010 008:000 N
02 00001 00016 003:000 N
03 00000 00000 000:000 N
04 00000 00000 000:000 N
05 00000 00000 000:000 N
06 00000 00000 000:000 N
07 00000 00000 000:000 N