SERVICE MANUAL EIS 165.3 N/P KW (short version) inglese
Autori: Serralunga M.
14/10/2021
18
NO COPYING IN ANY FORM WITHOUT WRITTEN PERMISSION FROM EPTA QUALITY MANAGEMENT
5.9
REFRIGERANT GAS CHARGING AND THERMODYNAMIC CIRCUIT
CLOSING.
Check the refrigerant charge on the data label inside the cabinet.
Using a refrigerant scale (
7
), verify the quantity of refrigerant gas in the gas bottle (
8
).
REFRIGERNAT CHARGE:
Lateral Side Circuit:
Refrigerant Charge 130 g
Central Side Circuit:
Refrigerant Charge 140 g
Disconnect the vacuum machine from the low pressure pipe (
A
); connect the gas bottle
(
8
) to the circuit.
WARNING! in order to avoid damages on the thermodynamic system or danger for
technical assistant; be sure to have connected the gas bottle to the refrigerator circuit.
The refrigerator must be ON for 5-6 minutes, then disconnect the refrigerator from current.
8
7
R
2
9
0