4. Troubleshooting (PROFIBUS DP)
4.2.3.6.2 Verifying the PROFIBUS DP network condition
The applicomIO Console application has the following functions:
Network Monitor function: Monitoring error condition detected on the
network
Diagnostic function:
Network diagnosis
(1) Select the
Network Detection
tab in the left center of the applicomIO Console
application.
(2) Click the
Online Action
button. The
Network Monitor
dialog appears.
You can check the conditions of the following errors on this dialog.
Token Error
Address Error
Timeout Error
Frame Error
Network Cycle
Bus Fault
When an error occurs on the network, it is added to the corresponding error
counter.
Fieldbus I/O Rev.6
137