2.3.3
Installing the device
•
Select the location for the device so that the connection to the load resp. source is as short as possible.
•
Leave sufficient space, at least 30 cm (1 ft), behind the equipment for ventilation (only required for the
standard air-cooled version)
•
The device must not be operated without a proper touch protection for the AC connection, which is either
only accomplished by installation of the device in a 19” rack/cabinet with lockable doors or by applying
further measures (additional cover etc.)
All models in this series require to be installed and operated in a closed appliance, such as a cabinet. It’s also mandatory to
install a rigid AC connection. Open operation on a desk or similar isn’t permissible.
A device in a 19” chassis will usually be mounted on suitable rails and installed in 19” racks or cabinets. The depth of the
device and its weight must be taken into account. The handles on the front are for sliding in and out of the cabinet. Slots on
the front plate are provided for fixing the device (fixing screws not included).
The unacceptable positions, as shown below, are also valid for the vertical mount of the device onto a wall (room or inside a
cabinet). The required air flow would be insufficient.
Acceptable and unacceptable installation positions (air or water cooled, air cooled shown):
Standing surface