EPS Stromversorgung GmbH
Alter Postweg 101 • 86159 Augsburg
Germany
Fon: +49 821 / 570451-0
Fax: +49 821 / 570451-25
www.eps-germany.de
PSB 9000 3U Slave Series
15 kW
Model Slave
PSB 9500-90
PSB 9750-60
PSB 91000-40
PSB 91500-30
Power regulation
Adjustment range
0…15.3 kW
0…15.3 kW
0…15.3 kW
0…15.3 kW
Accuracy
(1
(at 23 ± 5°C)
< 1% P
Max
< 1% P
Max
< 1% P
Max
< 1% P
Max
Line regulation at ±10% ΔU
AC
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
< 0.05% P
Max
Load reg. at 10-90% ΔU
OUT
* ΔI
OUT
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
< 0.75% P
Max
Efficiency
(2
~ 95%
~ 95%
~ 95%
~ 95%
Internal resistance regulation
Adjustment range
0.16...340 Ω
0.4...740 Ω
0.8...1300 Ω
2.5..3000 Ω
Accuracy
(1
≤ 2% of max. resistance ± 0.3% of maximum current
Insulation
Allowed float (potential shift) on the DC terminal:
Negative terminal to PE
Max. ±1500 V DC
±1500 V DC
±1500 V DC
±1500 V DC
Positive terminal to PE
Max. ±1800 V DC
±1800 V DC
±1800 V DC
±1800 V DC
AC input <-> PE
2.5 kV DC
AC input <-> DC terminal
2.5 kV DC
Miscellaneous
Cooling
Temperature controlled fans, front & side inlet, rear exhaust
Ambient temperature
0..50°C
Storage temperature
-20...70°C
Humidity
< 80%, not condensing
Standards
EN 61010-1, EN 50160:2011-02, EN 61000-6-2:2016-05, EN 61000-6-3:2011-09
Overvoltage category
2
Protection class
1
Pollution degree
2
Operational altitude
< 2000 m
Digital interfaces
Featured
1x USB (front side) for quick value setup
1x USB (rear side) for communication and service
Galvanic isolation from device
Max. 1500 V DC
Terminals
Rear side
Share Bus, DC terminal, AC input, remote sensing, USB, master-slave bus
Front side
USB
Dimensions
Enclosure (WxHxD)
19“ x 3U x 669 mm
Total (WxHxD)
483 x 133 x min. 775 mm
Weight
~ 32 kg
~ 32 kg
~ 32 kg
~ 32 kg
Article number
30090315
30090316
30090317
30090318
(1 Related to the nominal values, the accuracy defines the maximum deviation between an adjusted values and the true (actual) value