The Battery Control Voltage Parameters refer to chapter
WARNING
The (Utility/Generator) dry contact OFF interface is closed when the system is
powered off. Please check the system in time.
Refer to below the diagram:
2.5 Mounting
WARNING
Risk of explosion! Never install the controller in a sealed enclose with flooded
batteries! Do not install the controller in a confined area where battery gas can
accumulate.
Risk of electric shock! When wiring the solar modules, the PV array can produce a
high open-circuit voltage, so disconnect the breaker before wiring and be careful.
Tracer-AN series controllers have no battery reverse protection. Do not reverse
the battery during the wiring. Otherwise, the controller may be damaged.
CAUTION
The controller requires at least 150mm of clearance above and below for proper
airflow. Ventilation is highly recommended if mounted in an enclosure.
Installation procedures:
Step 1: Determine the installation location and heat-dissipation space
Ensure enough air flows through the controller's heat sink when installing the controller. Please leave at
least 150mm clearance away from the upper and lower edges.