Connecting a breaker in series in the solar circuit is recommended, and the
breaker must be 1.25 to 2 times of the rated current. Keep OFF before
connection. Connect solar positive (+) and negative (-) to solar terminals on
the controller in the figure 1-1
. Please pay much attention to ‗+‘ and ‗
-
‘
.
Solar array short circuit protection and the reversed polarity connection will
trigger automatically.
WARNING:
Risk of electric shock!
Use fuses or breakers in solar and battery circuits is recommended,
and make them keep OFF state before connection.
WARNING:
Risk of electric shock!
Exercise caution when handling solar wiring. The solar PV array can
produce open-circuit voltages in excess of 150 V when in sunlight.
Pay more attention to it.
WARNING:
Risk of explosion or fire!
Never short circuit battery positive (+) and negative (-) or cables.
Pay more attention to it
AVERTISSEMENT :
Risque d'électrochoc!
L'utilisation de fusibles ou coupe-circuits dans le module solaire, le
chargeur et les circuits de la batterie est recommandée, ils doivent
être tenus en position éteinte avant la connexion.
AVERTISSEMENT :
Risque d'électrochoc!
Faites attention lors de la manipulation des connexions solaires. La
matrice PV solaire peut produire des tensions supérieures à 150V, à
la lumière du soleil. Soyez particulièrement attentif à cela.
AVERTISSEMENT :
Risque d'explosion ou d'incendie!
Ne court-circuitez jamais les pôles positifs (+) et négatifs (-) de la
batterie ou les câbles. Soyez particulièrement attentif à cela.
2.5 Power Up
CAUTION:
The controller is only powered by battery, so it will not
work when connected only to solar input.
REMARQUE :
Le contrôleur n'est alimenté que par la batterie,
donc il ne fonctionnera que lorsque branché sur l'alimentation
solaire.