Technical data
3.1
Rating data PE
CON+
®
Testable networks
Single phase:
L / N / PE
3-phase with N: L1 / L2 / L3 / N / PE
Network configuration
TN-S system
Rated voltage
200..230 VAC (±10%)
Rated frequency
50 / 60 Hz (±5%)
Response lag
<0.4 s
Response threshold
<1000 Ω
Power loss
5 VA
Ambient temperature
Operation: -15...+40ºC
Storage: -25...+70ºC
Transport: -25...+70ºC
Rel. humidity
max. 98%, without condensation
Atmospheric pressure
70..106ºC,
Dimensions
75 x 45 x 125 mm
Weight
Approx. 400 g
Mounting / fitting
on TS35 mounting rail according to DIN EN 50022, installation
position as required
Connections
Mains connection: L / N
Protective earth terminal: PE
Release relay:
Alarm/operation (change-over
contact)
Other connections:
External Test key (break contact)
Contact rating
max. 250 VAC / 5 A; 30 VDC / 2 A
Cable cross-section
max. 4.0 mm² (12 AWG) solid
max. 2.5 mm² (14 AWG) flexible with sleeve
Tightening torque
max. 0.8 Nm
LED displays
green:
OK (operating mode display)
yellow:
Phase an N (polarity reversal L / N)
red:
Alarm (PE interruption)
_
Function test
via test key on front cover or ext. test key
Protection class
IP20 (terminals), IP40 (housing)
Direct contact protection
DGUV V3 (BGV A3)
Flammability
UL94 V-0
Housing material
PC-GF
Normative basis
DIN EN 50178 / VDE 0160:1998-04
Safety
DIN EN 61010-1, DIN EN 60204-1
EMC
DIN EN 61326-1, DIN EN 55011
Conformity
CE, RoHS (2011/65/EU),
LVD (2006/95/EG), EMCD (2004/108/EG), MD (2006/42/EG)