3.3.6 Switching hysteresis for the IR temperature
In the service settings, you can also set a temperature range within which
the IR emitters are switched on and off. It applies to all connected IR emit-
ters.
Example — 46°C target temperature and hysteresis 4 K:
The IR emitter is
switched off at 48°C and switched on at 44°C.
Adjusting the hysteresis
1
Tap and hold
for 3 seconds.
2
Enter code
5349
and confirm.
3
Tap
and confirm the selection.
4
Set the value with
and
, and then confirm.
The value can be set to any number between 1 and 5.
3
K
Setting
Switch. hysteresis