6. After completed installation and correct
commissioning of the control unit, the line
for overtemperature protection must be
checked for short-circuits. In order to do this,
disconnect one of the wires of the white ca-
ble in the sensor casing. The respective error
message appears in the display. Reconnect
the wire to make the message disappear.