E90-803-001-005-01 – Rev 4
- 12 -
H – Filter
A – Bypass washer
The fuel filter and bypass washer are
located within the pump housing. By
removing the 4 fixing screws the housing
can be removed allowing access.
The bypass washer is located under the
bottom of the 3 internal screws.
In case of one-pipe operation the
horseshoe-shaped copper washer will be
mounted under the screw head, and in
case of two-pipe operation, the horseshoe-
shaped copper washer will be removed.
1
2
3
4
5
6
Fuel pump type Danfoss BFP11 R3
Technical data
1 or 2 pipe operation
Oil Viscosity range: 1.3 – 12.0 cSt
Pressure range: 7 – 15 bar
Oil temperature: -10 - +70ºC
1 - Nozzle port 1/8”
2 - Vacuum gauge port 1/8”
3 - Suction line port 1/4”
4 - Return line port 1/4”
5 - Pressure adjustment (4mm allen key)
6 - Pressure gauge port 1/8”