
Installation, Start-Up, Adjustment and Maintenance Manual
32
If power for the water pump is taken from the high voltage terminal block located in the electrical control
box, as show in Figure 15, the minimum circuit ampacity for the unit must be increased above that
listed in the TECHNICAL DATA sheet in SECTION 2 to accommodate the additional current draw of
the water pump installed.
The maximum current carrying capacity of th
e N.O. C
ontact is 4A.
If the
current is above 4A, use an additional relay controlled by N.O. Contact on the S-60 board.
5.2 PUMP WIRING
CONTROLLED BY THE UNIT
When the hydronic system’s water pump is controlled by the unit, the installer must keep in mind the
circuit ampacity, the required water pump voltage, and the current carrying capacity of the N.O.
Contact on the electronic control board.
When controlled by the S-60 board, the water pump operates while the control switch is closed.
The N.O. Contact will open 215 seconds after the control switch opens.
-
Wiring a 230 volt water pump with a current requirement less than 4 amperes, see Figure 18.
-
Wiring a 230 volt water pump with a current requirement greater than 4 amperes, see Figure 16.
-
Wiring a 115 volt water pump with a current requirement less than 4 amperes, see Figure 17.
-
Figure 16
–
WIRING A 230 VOLT WATER PUMP THAT EXCEEDS ELECTRONIC BOARD’S 4A RATING
Figure 17
–
WIRING A 115 VO
LT WATER PUMP THAT MEETS ELECTRONIC BOARD’S 4A RATING
EXTERIOR CONTROL
When the unit does not control the hydronic system’s water pump, the installer must ensure that the
pump and the unit start at the same time. Also, the pump must continue to run during
the unit’s cycle
down time (215 seconds after the opening of the control switch). See Figure 18.
L2
L2
L1
L1
N.O. CONTACT
(4A MAXIMUM)
230 VOLT
WATER PUMP
DPST (N.O.)
RELAY WITH
230 VOLT
COIL
L2
L2
L1
L1
NEUTRAL
HIGH VOLTAGE
TERMINAL BLOCK
HIGH VOLTAGE
TERMINAL BLOCK
N.O. CONTACT
(4A MAXIMUM)
115 VOLT
WATER PUMP
WARNING
NOTE