Installation, Start-Up, Adjustment and Maintenance Manual
30
The chiller and its individual shut-off valve must be disconnected from the gas supply piping system
during any pressure testing of the gas piping system at test pressures
in excess of 1/2 psig.
The chiller must be isolated from the gas supply piping system by closing its individual shut-off valve
during any pressure testing of the gas piping system at test pressures
equal to or less than 1/2 psig.
Figure 13
– TYPICAL GAS CONNECTION
Figure 14
– TYPICAL AC CONNECTIONS
APPROVED UNION
SEDIMENT TRAP
APPROVED GAS
SHUT-OFF VALVE
TO UNIT
FROM GAS
SUPPLY
3/8 Nom. (ID) W/Flare Type
Connections
220VAC
Pump Power