Initial Installation
QUALIFIED INSTALLERS ONLY
F
ReestanDing
D
RaFthooD
a
DaPtoR
- 50-841:
This Drafthood Adaptor is a complete assembly and is ready to fit onto your Westport in a vertical vent
application only. With the Drafthood Adaptor correctly installed and wired to the gas control valve. Your
Direct Vent Fireplace can be vented like a B-Vent Fireplace.
INSTALLATION:
WARNING:
This Freestanding Drafthood Adaptor must be fitted by a qualified service technician.
1.
Remove the Drafthood Adaptor from the packaging. Ensure the unit and wire harness are undamaged. If
there is damage contact your dealer, distributor, or courier company before starting this installation.
2.
Install the adaptor so the wires exit to the rear of the fireplace. Slide the Drafthood Adaptor over the
outlet pipe of the fireplace until the bottom of the adaptor collar stops on the top of the outlet. The
Drafthood Adaptor must be safely secured to the vent flanges with either self-tapping screws and/or
high temperature sealant.
WARNING:
During the fitting of the Drafthood Adaptor, ensure that the wires are not pinched between
the adaptor and the collar and/or flue outlet. Ensure that the opening of the Drafthood Adaptor is not
blocked or obstructed.
3.
Being careful not to run any wiring tight across metal edges; connect them to the valve and “ON/OFF”
switch (refer to Figure 45).
Figure 45: Wiring Diagram for Electrical Connection.
4. Adjust the restrictor plate
to position 2.5 of 5. See the
vent restrictor settings in
the instruction manual.
5. Adjust the embers on the
burner so they don’t cover
the burner ports.
WIRING DIAGRAM:
The fireplace connections
are labelled in Figure 45.
When installing the Drafthood
Adaptor onto a fireplace fitted
with an intermittant pilot
system, remove the Main On/
Offone wire loop from the
IFC and replace it with the
drafthood adapter wires as
shown.
GENERAL VENTING INFORMATION:
Canadian Installations
The venting system must be installed in accordance with the current CSA B149 installation code and/or
local codes having jurisdiction.
U.S.A. Installations
The venting system must be installed in accordance with the current National Fuel Gas Code, ANSI
Z223.1, and/or local codes having jurisdiction.
36
IFC (50-3202) /
(0.584.326)
Main On/Off
(50-3205)
Drafthood adaptor
300
o
F (149
o
C)
manual reset
temperature
sensor