Installation

C

HimneY

 i

nstAllAtion

 t

HrougH

 w

All

:

Here are four (4) methods of combustible wall chimney connector pass-throughs. Information was provided from NFPA 211.

Method A

. 12” (304.8 mm) Clearance to Combustible Wall Member: 

Using a minimum thickness 3.5” (89 mm) brick and a ⅝” (15.9 mm) 

minimum wall thickness clay liner, construct a wall pass-through.  The 

clay liner must conform to ASTM C315 (Standard Specification for Clay 

Fire  Linings)  or  its  equivalent.  Keep  a  minimum  of  12”  (305  mm)  of 

brick masonry between the clay liner and wall combustibles.  The clay 

liner shall run from the brick masonry outer surface to the inner surface 

of the chimney flue liner but not past the inner surface.  Firmly grout or 

cement the clay liner in place to the chimney flue liner.  

Method B

. 9” (229 mm) Clearance to Combustible Wall Member: Using 

a 6” (152 mm) inside diameter, factory-built Solid-Pak chimney section 

with  insulation  of  1”  (25.4  mm)  or  more,  build  a  wall  pass-through 

with  a  minimum  9”  (229  mm)  air  space  between  the  outer  wall  of 

the chimney length and wall combustibles. Use sheet metal supports, 

fastened securely to wall surfaces on all sides, to maintain the 9” (229 

mm) air space.  When fastening supports to chimney length, do not 

penetrate the chimney liner (the inside wall of the Solid-Pak chimney). 

The inner end of the Solid-Pak chimney section shall be flush with the 

inside of the masonry chimney flue and sealed with a non-water soluble 

refractory cement. Use this cement to also seal to the brick masonry 

penetration.

Method  C

.  6”  (152.4  mm)  Clearance  to  Combustible  Wall  Member: 

Starting with a minimum 24 gauge (.024” [0.6 mm]) 6” (152.4 mm) 

metal  chimney  connector  and  a  minimum  24  gauge  ventilated  wall 

thimble which has two air channels of 1” (25.4 mm) each, construct a 

wall pass-through. There shall be a minimum 6” (152.4 mm) separation 

area containing fiberglass insulation, from the outer surface of the wall 

thimble  to  wall  combustibles.  Support  the  wall  thimble  and  cover  its 

opening with a 24 gauge minimum sheet metal support. Maintain the 

6” (152.4 mm) space. There should also be a support sized to fit and 

hold the metal chimney connector. See that the supports are fastened 

securely to wall surfaces on all sides. Make sure fasteners used to secure 

the metal chimney connector do not penetrate chimney flue liner.  

Method  D

.    2”  (50.8  mm)  Clearance  to  Combustible  Wall  Member:

 

Start with a solid-pak listed factory-built chimney section at least 12” 
(304 mm) long, with insulation of 1” (25.4 mm) or more, and an inside 
diameter of 8” (2” [51 mm] larger than the 6” [152.4 mm] chimney 
connector). Use this as a pass-through for a minimum 24 gauge single-
wall  steel  chimney  connector.  Keep  solid-pak  section  concentric  with 
and spaced 1” (25.4 mm) off the chimney connector by way of sheet 
metal support plates at both ends of chimney section.  Cover opening, 
and support chimney section on both sides, with 24 gauge minimum 
sheet metal supports. See that the supports are fastened securely to 
wall  surfaces  on  all  sides.

 

Make  sure  fasteners  are  used  to  secure 

chimney flue liner.

Chimney flue

Masonry 

chimney

Sheet steel supports

Chimney 

connector

Minimum chimney clearance from masonry to sheet

steel supports and combustibles 2 inches (50.8 mm)

Two air channels each

1 inch (25.4 mm)

Minimum 6 inches

(152.4 mm) glass

fiber insulation

Two ventilated air channels

each 1 inch (25.4 mm).

Construction of sheet steel

Minimum 12 inches

(304.8 mm) to combustibles

Masonry

chimney

Fire clay liner

Chimney

connector

Minimum clearance

12 inches (304.8 mm)

of brick

Minimum chimney clearance to brick

and combustibles 2 inches (50.8 mm)

Chimney Flue

Minimum chimney clearance from masonry to sheet

steel supports and combustibles 2 inches (50.8 mm)

Factory-built

chimney length

Non-soluble

refractory

cement

Chimney length

flush with inside

of flue

Air space 9 inches

(228.6 mm) minimum

Chimney flue

Masonry chimney

Sheet steel supports

Solid-insulated,

listed factory-built

chimney length

Use chimney

manufacturer’s

parts to attach

connector securely

Chimney 

connector

Minimum clearance

9 inches (228.6 mm)

NOTES:

1. Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall pass-through 

system and the chimney wall, to but not past the inner flue liner face.

2. A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a floor, or ceiling.

Figure 26: Chimney Through Wall - Method A.

Figure 27: Chimney Through Wall - Method B.

Figure 29: Chimney Through Wall - Method D.

Figure 28: Chimney Through Wall - Method C.

Summary of Contents for Kodiak 1200 Fireplace Freestanding

Page 1: ...NJURY OR EVEN DEATH Contact your local building or fire officials or the authority having jurisdiction about restrictions and installation inspection requirements in your area This heater meets the U...

Page 2: ...Insert 24 Hearth Protection Examples 25 Outside Air Kit 28 Recommended Heights And Diameters For Flue Pipe 28 Chimney Installation Through Wall 29 Installation of A Listed Factory Built Chimney Frees...

Page 3: ...back of the pedestal Do not burn coal or charcoal as there is danger of carbon monoxide being produced Do not use chemical fluids to start or re fresh the fire Do not burn garbage or flammable fluids...

Page 4: ...d drop into the ash pan Ensure that the trap door is closed properly before relighting the unit When the ash drawer is ready to be emptied lift the front of the drawer up then slowly pull the drawer s...

Page 5: ...ute materials are allowed CLEANING THE PLATED SURFACES Painted faces should be wiped with a damp cloth periodically If a plated door has been purchased it should be unpacked carefully to avoid getting...

Page 6: ...l cardboard or loose paper can produce soot or large flakes of char or fly ash that can coat the combustor causing smoke spillage into the room and rendering the combustor ineffective 2 Building Maint...

Page 7: ...it Never use coated typically advertising flyers or coloured paper b Always open the door of the wood stove slowly to prevent suction and drawing smoke into the room c Crumple several pieces of paper...

Page 8: ...s for starting a fire mean perfect results every time The quick answer is most of the time There are many variables that may affect your success when starting a fire Most of those variables and how to...

Page 9: ...be seen d Chimney Installation and Maintenance Avoid using too many elbows or long horizontal runs Too short a chimney can cause difficult start up dirty glass back smoking when door is open and even...

Page 10: ...easoned wood Primary air window airwash Pilot air Slider plate used for air flow control Primary air window airwash Pilot air Slider plate used for air flow control 1 2 Ceramic baffle reflects heat do...

Page 11: ...mm x 464 mm x 283 mm Capacity 1 85 feet3 0 0526 meter3 Approximate heating area 2200 feet2 205 meter2 E P A output rating 11 479 to 34 196 BTU hour 3 361 to 10 013 watt Duration on low burn 6 10 hours...

Page 12: ...m x 464 mm x 304 mm Capacity 2 5 feet3 0 0708 meter3 Approximate heating area 3000 feet2 280 meter2 E P A output rating 9 425 to 31 780 BTU hour 2 760 to 9 306 watt Duration on low burn 8 12 hours Wei...

Page 13: ...n combustible spacers 14 357 mm Ceramic tiles or eqivalent non combustible material on non combustible supports with a minimum of 013 0 33mm sheet metal spaced out 1 25mm by non combustible spacers 10...

Page 14: ...n combustible spacers 16 408 mm Ceramic tiles or eqivalent non combustible material on non combustible supports with a minimum of 013 0 33mm sheet metal spaced out 1 25mm by non combustible spacers 12...

Page 15: ...rth pad USA 6 152 mm CND 8 200 mm USA 6 152 mm CND 8 200 mm USA 6 152 mm CND 8 200 mm USA 6 152 mm CND 8 200 mm Alcove 48 1220 mm Deep I Total Width 55 1397 mm J Total Height 78 1981 mm K Top of stove...

Page 16: ...of hearth pad USA 6 152 mm CND 8 200 mm USA 6 152 mm CND 8 200 mm USA 6 152 mm CND 8 200 mm USA 6 152 mm CND 8 200 mm Alcove 48 Deep I Total Width 51 1295 mm J Total Height 72 1829 mm K Top of stove t...

Page 17: ...ersized Surround 333 16 709mm 337 8 860mm 461 8 1171mm 161 2 419mm Min 131 4 337mm Max 1415 16 380mm 5 127mm 19 482mm 227 8 580mm 191 16 484mm or 199 16 497mm 2011 16 525mm 205 16 516mm 273 4 705mm 22...

Page 18: ...467mm Regular Surround 2715 16 709mm Oversized Surround 333 16 709mm 191 16 484mm or 199 16 497mm 21 533mm Min 173 4 452mm Max 197 16 495mm 5 127mm 231 2 596mm 273 8 695mm 191 16 484mm or 199 16 497mm...

Page 19: ...16 570mm 5 15 16 151mm 16 1 2 419mm 26 3 8 670mm 14 3 4 375mm 3 7 8 98mm 20 508mm 15 13 16 402mm 9 15 16 252mm 31 1 4 793mm 32 3 4 831mm 10 254mm Pedestal same height 13 7 16 341mm 22 7 16 570mm 18 3...

Page 20: ...718mm 24 1 2 622mm 21 534mm 5 15 16 151mm 23 1 16 586mm 10 254mm Pedestal same height 26 15 16 684mm 16 406mm 26 3 8 670mm 16 3 4 426mm 9 15 16 252mm 31 1 4 794mm 32 11 16 831mm 24 3 8 619mm 15 7 8 4...

Page 21: ...ng Side Dimensions For Fan Kit 4 104mm 5 3 8 137mm 2 3 4 69mm 10 3 8 264mm 4 102 mm 5 1 16 128 mm 5 3 8 137 mm 10 3 8 263 mm Figure 12 1200 Freestanding with Fan Kit Dimensions Figure 13 1700 Freestan...

Page 22: ...cation ready for installation If fresh air supply is being supplied from the bottom of the unit please install the cover plate supplied to the rear of the pedestal covering the 4 10 cm hole Note In se...

Page 23: ...nnector Heat Shield Loosen screws Flue The heat efficiency shield is installed to lower the clearances to combustibles on the flat top freestanding model 1 The unit must be in position for the install...

Page 24: ...Surround Panel 1 Fasten the Surround Spacer to the inner top surface of the Surround Panel using the four 4 T 20 screws refer to Figure 19 2 Refer to Installation Of The Surround Panel Insert to finis...

Page 25: ...Examples of Parallel Installation Using Clearances From Tables 9 10 refer to Figure 22 Model Country I Far Edge of Hearth Pad to Side Wall Minimum J Front of Hearth Pad to Back Wall Minimum Single Wa...

Page 26: ...03mm USA 6 152mm CND 8 203mm 59 1499mm 361 2 926mm 331 4 844mm Optional Coverage Optional Coverage Optional Coverage Door Opening 171 2 445mm 171 2 445mm 651 4 1657mm 16 406mm 6 152mm 461 2 1181mm 6 1...

Page 27: ...3 88mm 4 125mm USA 65 1657mm 59 1499mm 33 844mm 36 926mm 0 0mm 0 0mm Double Wall Pipe 1200 Canada 59 1522mm 56 1439mm 28 713mm 27 707mm 6 160mm 8 227mm USA 57 1471mm 53 1368mm 28 713mm 31 809mm 2 59m...

Page 28: ...4 15 4 17 1 16 2 18 6 5000 6000 14 4 15 2 16 0 16 0 17 6 16 8 19 2 6000 7000 14 9 15 7 16 5 16 5 18 2 17 4 19 8 7000 8000 15 4 16 3 17 0 17 0 18 8 17 9 20 5 8000 9000 15 8 16 8 17 6 17 6 19 4 18 5 21...

Page 29: ...y to wall surfaces on all sides Make sure fasteners used to secure the metal chimney connector do not penetrate chimney flue liner Method D 2 50 8 mm Clearance to Combustible Wall Member Start with a...

Page 30: ...ances If floor joists or ceiling rafters must be cut they must be made structurally sound again Install chimney according to chimney manufacturers instructions A chimney connector cannot pass through...

Page 31: ...ts with silicone caulking 12 Fasten the rain cap spark arrestor cap to the top of your chimney 13 Place the stove back into Figure 32 Standard Horizontal Installation position 14 Install the chimney c...

Page 32: ...e National Fire Protection Association NFPA Make sure there are no cracks loose mortar or other signs of deterioration and blockage Have the chimney cleaned before the stove is installed and operated...

Page 33: ...Fireplace is not altered beyond the damper or ash shelf being modified In Canada Insert Mobile Home installations must be pre approved by the local inspector All freestanding installation requirement...

Page 34: ...nnectors must be installed in accordance with the manufacturer s instructions Use only specified components The chimney and pipe must extend at least 10 feet 2 4 m above the stove and 3 feet 0 9 m abo...

Page 35: ...6 stainless steel liner that goes directly to the top of the chimney and is covered with a rain cap The chimney top is sealed with a flashing or steel plate that supports the weight of the chimney lin...

Page 36: ...re 39 Insert Installation into existing floor level masonry fireplace Installation Floor Protection Combustible Floor Masonry Fireplace 8 203 mm USA 16 406 mm CND 18 450 mm Figure 38 Insert Installati...

Page 37: ...face plate Let the silicon or cement dry 2 To make the installation of the surround panel onto the unit easy have the unit 6 150mm out from the fireplace 3 Push the insert into the fireplace allowing...

Page 38: ...to the front of the fireplace opening Refer to Step 3 NOTE In general masonry fireplaces have square fireboxes while zero clearance metal fireplaces have domed firebox tops Therefore zero clearance b...

Page 39: ...lock off plate Damper must be removed Zero clearance metal firebox IMPORTANT DO NOT modify any part of the ZC fireplace 7 After installing the unit into place and the pipe through the block off plate...

Page 40: ...holes and tap it with a hammer mallet to the left until the right end of the tube is freed To installation a secondary air tube reverse the above instructions IMPORTANT All secondary air tubes must b...

Page 41: ...holes and tap it with a hammer mallet to the left until the right end of the tube is freed To installation a secondary air tube reverse the above instructions IMPORTANT All secondary air tubes must b...

Page 42: ...are removable therefore please keep out of the reach of children under 3 5 Please clean all fingerprints off of all plated surfaces with denatured alcohol on a soft cloth before firing the unit each t...

Page 43: ...he plug DO NOT route the power cord beneath the heater WARNING This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged into a proper...

Page 44: ...n controller Power Supply Black Black Rocker Switch Manual Auto Off Black Fan White Black Fan temperature sensor White Black Power Supply Fan controller Installation Figure 54 Freestanding Fan Kit Wir...

Page 45: ...he box and inspect for any damage to the assembly If damage is noticed call your dealer distributor or courier company and have components replaced before installing kit 2 Remove the knock out at the...

Page 46: ...nto a bent over tab at the top of the shroud see A in Figure 58 5 To remove the shrouds loosen the two 2 torx T 20 screws that hold the shroud to the unit See B in Figure 58 Pull the shroud forward pa...

Page 47: ...gure 63 Installation of Panel the top and a side trim snug together use a flat head screwdriver to turn the two 2 screws in the bracket to tighten it into the trim 3 Slide the two 2 attached trim piec...

Page 48: ...manufacturers installation and operating instructions Contact local building or fire officials about restrictions and installation inspection in your area Use 6 150 mm diameter minimum 24 MSG black o...

Page 49: ...ash drawer Nickel 50 979 11 1200 Leg Kit with ash drawer Gold 50 980 11 1200 Leg Kit with ash drawer Painted 50 981 11 1200 Leg Kit with ash drawer Brushed Nickel 50 1470 12 1200 Freestanding Pedestal...

Page 50: ...Leg Kit Ash Drawer Box 50 1132 39 1700 Leg Kit Ash Drawer Box 50 1133 40 1200 Leg Kit Adaptor Plate 50 1134 41 1700 Leg Kit Adaptor Plate 50 1135 42 1200 1700 Pedestal Kit Ash Drawer 50 1136 43 1200 1...

Page 51: ...51 Parts Diagram Freestanding 32 31 35 36 30 29 33 32 16 18 20 19 46 26 44 5 28 8 10 27 15 3 1 7 18 22 21 24 23 25 43 45 9 17 Kodiak Freestanding Components April 2013 50...

Page 52: ...Parts Diagram Pedestals Legs 12 14 11 13 42 40 41 6 39 37 38 Kodiak Pedestal and Leg Kit Components March 2008 52...

Page 53: ...53 Parts Diagram Fireplace Insert 52 16 56 9 47 53 51 54 55 4 2 Kodiak Fireplace Insert Components April 2013 1 48 3 49 Common parts are shown in Parts Diagram Freestanding...

Page 54: ...serial number Exclusions An expanded list of exclusions is available at www enviro com help warranty html This warranty does not cover Damage as a result of improper usage or abuse Damage caused from...

Page 55: ...________________ _________________________________________ PHONE ___________________________________ MODEL ___________________________________ SERIAL NUMBER ___________________________ DATE OF PURCHAS...

Reviews: