background image

VENT TERMINAL CLEARANCES 

 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

A= Clearance above grade, verandah, porch, deck, or 

balcony [*12 inches (30 cm) minimum] 

 

5

B= Clearance to window or door that may be opened  

[*12 inches (30 cm) minimum] 

C= Clearance to permanently closed window        

[minimum 12 inches (30 cm) recommended to prevent 
condensation on window] 

D= Vertical clearance to ventilated soffit located above the 

terminal within a horizontal distance of 2 feet (60 cm) 
from the center-line of the terminal (24 inches (60 cm) 
minimum) 

E= Clearance to unventilated soffit 

[18 inches (45 cm) minimum] 

F= Clearance to outside corner [12 inches minimum] 
G= Clearance to inside corner [`12 inches minimum] 

H= *Not to be installed above a meter/regulator assembly 

within 3 feet (90 cm) horizontally from the center-line of 
the regulator 

I= Clearance to service regulator vent outlet  

[*6 feet (1.8m) minimum] 

J= Clearance to non-mechanical air supply inlet to building 

or the combustion air inlet to any other appliance  
[12 inches (30 cm) minimum] 

K= Clearance to a mechanical air supply inlet  

[*6 feet (1.8m) minimum] 

L=*** Clearance above paved side-walk or paved driveway 

located on public property  
[*7 feet (2.1m) minimum] 

M= Clearance under verandah, porch, deck, or balcony 

[*24 inches (60 cm) minimum **] 

 

*** 

A vent shall not terminate directly above a sidewalk or paved driveway, which is located between two single family dwellings 

and serves both dwelling  
**  Only permitted if verandah. Porch, deck, or balcony is fully open on a minimum of 2 sides beneath the floor 
As specified in CGA B149 Installation Codes (1991) Note: Local Codes or Regulation 

 

WHEN VENTING THIS APPLIANCE YOU MUST STAY WITHIN THE 
SHADED AREA (see venting chart provided) FOR ALL VENTING 
APPLICATIONS. 

Installations over 15 feet 

(4.5m) vertical require the 

use of a vent restrictor 

 

VENT RESTRICTOR RING:

 A vent restrictor ring is supplied with each 

direct vent fireplace. This restrictor ring is to be installed when the vertical 
chimney installation is over 15’ (4.57 M). Before the chimney is placed onto 
the stove, place this vent restrictor ring into the 4” (10.16 CM) flue pipe(as 
shown), once the vent restrictor ring has been installed, the vertical sections 
of chimney can 

be installed. 

 

Summary of Contents for EG 28

Page 1: ...tely call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING If the information in this manual is n...

Page 2: ...stallation must conform to local codes or in the absence of local codes with the current CAN 1 B 149 installation code in Canada or the current National Fuel Gas Code ANSI Z223 1 in the USA To prevent...

Page 3: ...tural or propane gases see control panel and rating label are not for use with solid fuels must not be connected to a chimney flue serving a separate solid fuel burning appliance are approved for bedr...

Page 4: ...re the flue system of the stove can be properly installed without damaging the integrity of the building e g cutting a wall or ceiling joist The stove can be installed on any standard flooring materia...

Page 5: ...to a mechanical air supply inlet 6 feet 1 8m minimum L Clearance above paved side walk or paved driveway located on public property 7 feet 2 1m minimum M Clearance under verandah porch deck or balcony...

Page 6: ...HE OUTSIDE VENT TERMINATION BEFORE BEGINNING THE INSTALLATION TAKE CARE TO ENSURE AN APPROPRIATE OUTSIDE LOCATION FOR THE VENT TERMINATION CAN BE ACCOMMODATED FOLLOW THE VENT LENGTH DIAGRAM PRECISELY...

Page 7: ...shown in FIG 10 NOTE 1 Twist lock procedure four indentations located on the female end of the pipes and fittings are designed to slide straight onto the male ends of adjacent pipes and fittings by o...

Page 8: ...excessive heat from possibly melting the vinyl siding material Note that the horizontal vent termination bolts onto the flat portion of the vinyl siding standoff shaded area in FIG 12 so that an air...

Page 9: ...pipe and elbows may be utilized in the attic as well as above the roofline The galvanized finish is desirable above the roofline due to the higher corrosion resistance STEP 6 Once the pipe sections h...

Page 10: ...quired at the second floor and any subsequent floors FIG 19 The opening should be framed to 10 inch x 10 inch inside dimensions in the same manner as shown in FIG 16 2 Any occupied areas above the fir...

Page 11: ...ide on a location for the unit that will meet any or all local code requirements Refer to sections in this manual Deciding Were To Locate Your Stove and Planning Your Installation Set the appliance in...

Page 12: ...liner over collar secure the flex liner with 3 sheet metal screws evenly spaced Align all straight sections of pipe slipping all joints together and installing 3 sheet metal screws evenly spaced A sm...

Page 13: ...minimum 4 flex liner to the top of the CLASS A chimney Placing a bead of high temperature silicone to the Simpson Cap adapter and securely attach the flex liner to the adapter Secure the cap adapter t...

Page 14: ...EVER OPERATE THIS APPLIANCE WITH THE DOOR REMOVED INSTALLING THE LOGSET INSTALLING THE LOGSET Carefully remove log from box Check to ensure there is no damage It is very important to install this log...

Page 15: ...f all electrical power to the appliance 3 Turn the gas control knob clockwise to the off position 4 Open door Wait five 5 minutes to clear out any gas Close door If you smell gas including near the fl...

Page 16: ...about the first two weeks of use After that depending upon the amount of use cleaning should be required no more than two or three times per season To clean the door use a mild glass cleaner and a sof...

Page 17: ...thermocouple Air in gas line Pilot flame dies while knob is depressed Bleed line Check gas line pressure Contact dealer Burners will not remain lit Problem with thermopile circuit Check gas line pres...

Page 18: ...ition of the National Fuel Gas Code ANSI Z223 1 UPON CONNECTION MARK APPROPRIATE FUEL TYPE ON RATING LABEL LOCATED ON THE INSIDE OF THE RIGHT HAND SIDE PANEL Manifold Pressure Tap Inlet Pressure Tap M...

Page 19: ...d securely to the floor WARNING ELECTRICAL GROUNDING INSTRUCTIONS This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged into a pro...

Page 20: ...ower does not require lubrication 20 1 Turn the unit off and remove the log set 2 Remove the burner tray assembly by removing the screw on either side of the tray between the front and rear burners Li...

Page 21: ...ided by S I T STEP 5 To change the pilot orifice First remove the two 2 T 20 Torx screws that hold the pilot assembly to the burner tray Lift the pilot assembly from the burner tray Using a 10mm wrenc...

Page 22: ...rts only thereafter The paint on the Metal Brick Liner may peel This is due to the extreme conditions applied to the paint and is no way covered under warranty Your dealer shall make all claims under...

Page 23: ...143 BURNER COMPLETE W NOVA SIT VALVE NG EC 024 SS FLEX CONNECTOR WITH 3 8 ELBOW 18 LONG EG28 145 BURNER COMPLETE W NOVA SIT VALVE LP EC 025 BURNER SWITCH FOR NOVA TRAY EG28 150 ASH SILL EC 029 FAN ACC...

Page 24: ...ET FS CABINET SIDE PANEL EG28 123 BV TOP BAFFLE EG28 132 DV TOP BAFFLE EG28 131 FS CABINET SIDE PANEL EG28 123 BV 4 CRIMPED FLUE PIPE EG28 169 DV 4 FLARED FLUE PIPE EG28 170 120 F 49 C CERAMIC FAN TEM...

Page 25: ...LASS A B EG28 101 BURNER CONTROL ASSEMBLY COMPLETE EG28 143 NG EG28 145 LPG FULLY ASSEMBLED PILOT EC 015 NG 016 LP THERMOPILE EC 012 THERMOCOUPLE EC 009 PILOT ORIFICE EC 019 NG 020 LP SPARK ELECTRODE...

Page 26: ..._______________________ Phone ___________________________________ Name of Installer ___________________________________________ Address _________________________________________ __ ___________________...

Reviews: