background image

When planning your installation, it will be necessary to select the proper length of vent pipe for your particular requirements. It 
is important to note when passing through a wall, the maximum allowable wall thickness is 10-inches (254 mm), 1 1/2” inches 
clearance to combustibles must be maintained. Select the amount of vertical rise desired for “vertical-to-horizontal” type 
installations. To determine the length of vent pipe required for vertical installations, measure the distance from the appliance 
flue outlet to the ceiling, the ceiling thickness, the vertical rise through the attic or second story, and allow for sufficient vent 
height above the roofline. For two story applications, A firestop is required at each floor level. If an offset is needed in the attic, 
additional pipe and elbows will be required. To connect the venting system to the appliance flue outlet, a twist-lock adapter is 
built into the appliance at the factory. 

HORIZONTAL INSTALLATION 

STEP 1. 

Set the appliance in the desired location. Check to determine if wall studs or roof rafters are in the way when the 

venting system is attached. If this is the case, you may want to adjust the location of the appliance. 

 
 

STEP 2.   

Direct vent pipe and fittings are designed with special twist-lock connections. Assemble the desired combination of 

the pipe and elbows to the appliance adapter with pipe seams oriented towards the wall or floor, as much out of view 
as possible. 

 

Place a bead of Mil-Pac on the outer edge of the inner exhaust pipe (non-flared end). Place a bead of high temperature 
silicone on the male edge of the outer pipe. Push the pipe sections completely together, then twist-lock one section clockwise 
approximately one-quarter turn, until the two sections are fully locked. The female locking lugs will not be visible from the 
outside, on the pipe. They may be located by examining the inside of the female ends as shown in FIG-10. 
 
 

NOTE: 

 

(1)

 Twist-lock procedure: four indentations, located on the female end of the 

pipes and fittings, are designed to slide straight onto the male ends of adjacent 
pipes and fittings, by orienting the four pipe indentations so they match and 
slide into the four entry slots on the male end. 

 
 
 
(2)

 Horizontal runs of vent pipe must be supported every three feet (3’ ). Wall 

straps are available for this purpose.

 

 
 

FIG. 10

 
STEP 3.

 With the pipe attached to the stove into the correct location, mark the wall for a 10 inch x 10 inch square hole. The 

center of the square hole should match the centerline of the horizontal pipe. Cut and frame the 10-inch x 10-inch 
hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of non-
combustible material 

i.e. 

masonry or concrete, a 7-inch hole

 

is acceptable. 

 
 

STEP 4.

 Position the horizontal vent termination in the center of the 10-inch square hole, and attach to the exterior wall with 

the four screws provided. Before attaching the Vent Termination to the exterior wall, run a bead of non-hardening 
mastic around the edges, so as to make a seal between the termination and the wall. The arrow on the vent 
termination should be pointing up, insure that the proper clearances to combustible materials are maintained. 

 
 

STEP 5. 

Slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the cap assembly. It is 
important that the vent pipe extend into the vent cap a sufficient distance with a minimum of 1 1/4” inch overlap. 
Secure the connection between the vent cap pipe and the vent cap by attaching the two sheet metal straps extending 
from the vent cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect 
the straps to the vent pipe. Bend any remaining portion of the sheet metal straps back towards the vent cap, so the 
decorative wall thimble FIG-13 will conceal it. 

 
 
 
 
 
 

 

10

Summary of Contents for EG 33

Page 1: ...AT TO DO IF YOU SMELL GAS Open windows Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s p...

Page 2: ...allation must conform to local codes or in the absence of local codes with the current CAN 1 B 149 installation code in Canada or the current National Fuel Gas Code ANSI Z223 1 in the USA To prevent i...

Page 3: ...e all been certified for use with either natural or propane gases see control panel and rating label Are not for use with solid fuels Must not be connected to a chimney flue serving a separate solid f...

Page 4: ...here it can be accessed by a gas supply line Locate the stove in a large and open room that is centrally located in the house This will optimize heat circulation and comfort As the stove could be equi...

Page 5: ...re that the top header above the framing opening is installed on the edge or upright this will maintain proper clearances to the vent pipe NOTE MAKE SURE THAT THE UNIT HAS BEEN INSTALLED SO THAT THE B...

Page 6: ...supplied The unit can now be enclosed with the rest of the house finishing Place a sheet of drywall around the unit covering the nailing flanges and stopping on the unit body Place the finished tile...

Page 7: ...PLIANCE YOU MUST STAY WITHIN THE SHADED AREA see venting chart provided FOR ALL VENTING APPLICATIONS VENT RESTRICTOR RING A vent restrictor ring is supplied with each direct vent fireplace This restri...

Page 8: ...inimum C Clearance to permanently closed window minimum 12 inches 30 cm recommended to prevent condensation on window D Vertical clearance to ventilated soffit located above the terminal within a hori...

Page 9: ...ption 908B 6 Pipe Length Black 907B 9 Pipe Length Black 906 B 12 Pipe Length Black 904 B 24 Pipe Length Black 903 B 36 Pipe Length Black 902 B 48 Pipe Length Black 911 B 11 to 14 5 8 Pipe Adjustable B...

Page 10: ...n the pipe They may be located by examining the inside of the female ends as shown in FIG 10 NOTE 1 Twist lock procedure four indentations located on the female end of the pipes and fittings are desig...

Page 11: ...nation bolts onto the flat portion of the vinyl siding standoff shaded area in FIG 12 so that an air space will exist between the wall and the vent termination NOTES 1 The horizontal run of vent pipe...

Page 12: ...pipe and elbows may be utilized in the attic as well as above the roofline The galvanized finish is desirable above the roofline due to the higher corrosion resistance STEP 6 Once the pipe sections h...

Page 13: ...required at the second floor and any subsequent floors FIG 19 The opening should be framed to 10 inch x 10 inch inside dimensions in the same manner as shown in FIG 16 2 Any occupied areas above the...

Page 14: ...mbly 4 Spread ember pieces in a single layer evenly across the front burner ember tray Place a single layer of embers on top of the front burner 5 Carefully avoid any clumping or large build ups Do no...

Page 15: ...f all electrical power to the appliance 15 HI LO knob Control knob 3 Turn the gas control knob clockwise to the off position 4 Open door Wait five 5 minutes to clear out any gas Close door If you smel...

Page 16: ...the joint in the tape in a bottom corner Close door Glass must be purchased from an Envirogas dealer No substitute materials are allowed CLEANING THE INSIDE OF THE FIREBOX Remove the log carefully fro...

Page 17: ...thermocouple Air in gas line Pilot flame dies while knob is depressed Bleed line Check gas line pressure Contact dealer Burners will not remain lit Problem with thermopile circuit Check gas line pres...

Page 18: ...ted from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kP...

Page 19: ...bracket in the center rear of the appliance Place blower over the two screws provided on the base of the appliance 4 Install the electrical box on either the left side of the appliance This electrical...

Page 20: ...ot injector Install the new pilot injector BE CAREFUL WHEN TIGHTENING THE PILOT FITTING YOU COULD BREAK THE CERAMIC IGNITER ELECTRODE STEP 6 Re install the pilot assembly in the reverse order of STEP...

Page 21: ...er The paint on the Metal Brick Liner may peel This is due to the extreme conditions applied to the paint and is no way covered under warranty Your dealer shall make all claims under this warranty in...

Page 22: ..._________ 22 Name of Installer ___________________________________________ Address _________________________________________ __ ___________________________________________ ____________________________...

Reviews: