EBER 1500 WITH 1 OR 2 REMOVABLE HEAT EXCHANGERS
AND ELECTRIC ELEMENT OPTION
•
Heat Exchanger Efficiencies for DHW Heating from 15°C to 60°C
•
Heat Exchanger Inlet Temperatures 80°C
➢
The Lower Heat Exchanger Heats 88% of the Tank
➢
The Upper Heat Exchanger Heats 52% of the Tank
ABREVIATIONS
CWI
Cold Water Inlet
HWO
Hot Water Outlet
R
Recirculation
VEN
Ventilation
CI
Coil Inlet
CO
Coil Outlet
S
Sensor
T
Thermostat
TR
Thermometer
EH
Electric Heating Element
HEAT EXCHANGER COMBINATIONS AVAILABLE
Lower Heat
Exchanger
Upper Heat
Exchanger
Total H.E.
Surface
3,2m
2
3,2m
2
6,4m
2
5,4m
2
3,2m
2
8,6m
2
5,4m
2
5,4m
2
10,8m
2
LOWER HEAT EXCHANGER EFFICIENCY
FLOW RATE
3,2m
2
Heat Exchanger Efficiency
5,4m
2
Heat Exchanger Efficiency
1800 Lt/h
49,10kW
65,30kW
2600 Lt/h
55,20kW
78,40kW
3900 Lt/h
62,20kW
91,10kW
UPPER HEAT EXCHANGER EFFICIENCY
FLOW RATE
3,2m
2
Heat Exchanger Efficiency
5,4m
2
Heat Exchanger Efficiency
1800 Lt/h
48,10kW
64,60kW
2600 Lt/h
54,50kW
79,20kW
3900 Lt/h
61,40kW
90,90kW