MAC 10 Original VE5 SERVICE MANUAL
PAGE 4
. Figure 1
II.
SERVICE: Removal and Replacement of the HEPA/ULPA
Filter (Standard Unit)
WARNING!
Disconnect the unit from the electrical power source before attempting any
service.
Tools Required:
Phillips Head Driver
Step 1.
Remove unit from ceiling.
Step 2.
Remove the 10 screws holding the HEPA/ULPA filter to the lid assembly.
Step 3.
Lift the lid assembly off the HEPA/ULPA filter (see Figure 2). Discard the used
filter as per requirements of the applicable regulations.
Note:
Before replacing with a new HEPA/ULPA filter, carefully inspect the new filter for
any visible damage. Also inspect the gasket in the “tee” bar to insure a tight seal.
Replace as necessary.
Step 5.
Replace with the new HEPA/ULPA filter and assemble by reversing the above
steps.
Figure 2
Lid Assembly
Prefilter
HEPA/ULPA
Filter