Model: EP.MINI
Connecting to the PC using RS 485 mode
ENTRY
PASS
To configure
MINI
unit address
(default: 00), press:
•
F1
•
123456
•
01 Enter
•
01 Enter
•
04 Enter
•
Key in new unit address (00 – 15)
•
ESC x3
17
When the implementation consists of more than 1 MINI to be connected to the
PC using the same bus/comport, the unit address for each MINI must be unique.
Only a total of 16 controllers can be connected to each bus/comport.
Purple (C-)
Purple (C-)
Grey (C+)
Grey (C+)
Grey (C+)
C-
C+
Purple (C-)
MINI 16
Unit Address: 15
MINI 2
Unit Address: 01
MINI 1
Unit Address: 00
PCC
(Pc Communicator)
RS 232: 10 meter
R
S2
3
2
P
o
w
e
r
Tx Rx
EntryPass Platform1
Server Access
Control System
RS 485: I000 meter (Maximum)