13
KT-400 Ethernet Four-Door Controller
Installation Manual
Technical Specifications
Type
Description
AC Power input (
KT-400
)
Transformer class 2, 120 VAC 75VA IN; 16 or 24 VAC OUT
AC Power input (
KT-400-EU
)
Transformer 230 VAC 50 Hz 100 VA IN, 16.5 VAC OUT
Battery back-up (
KT-BATT-12
)
12 VDC, 12 Ah battery is recommended when using electromagnet door lock
Operating Temperatures
For UL listed installations: 0°C to 49°C (32°F to 120°F) indoor use only
For EN50133 compliant installations: 5°C to 40°C (41°F to 104°F) indoor Group I
Humidity Level
93% max. (relative humidity non-condensing)
Cabinet Dimensions
(High-Wide-Deep)
37.59 cm (14.8 in) x 30.48 cm (12.0 in) x 12.57 cm (4.95 in)
Cabinet Weight (
KT-400
)
4.0 kg (8.82 lb)
Cabinet Weight (
KT-400-EU
)
7.0 kg (15.43 lb)
PCB dimension
23.11cm (9.1in) x 13.97cm (5.5in) x 4.06cm (1.6in)
Reader types
Wiegand, proximity, ABA Clock and Data, bar code, magnetic, integrated keypad,
smartcard and others
Reader power output
12 VDC and 5 VDC @ 1A max each, protected and supervised
Monitored points
(zone inputs)
16 monitored points (Z1 to Z16), NO/NC, without EOL (DRY), single EOL, double EOL and
1 fixed-function tamper switch input
Points maximum wiring
AWG #22 - 600 m (2,000 ft)
Door strike power supervised
•
500 mA each or 2.0 Amps total for the
KT-400
model (JP4 on
INT
)
•
1 A each or 4.0 Amps total for the
KT-400
model (JP4 on
EXT
)
•
750 mA each or 3.0 Amps total for the
KT-400-EU
model (JP4 on
INT
)
Auxiliary reader outputs
LEDs (LED, OUT1 and OUT2) and buzzer (BUZ) for each individual door,
25mA max each, open collector outputs
Relay controlled output
4 onboard Form C Relay controlled outputs, 30 VDC, 3 Amps max each
Communication ports
1 x RS-232 with RJ-12, 2 x RS-485, 2 x Ethernet 10/100 Base-T with RJ-45
Expansion port
1 x SPI 6-pin connector, bidirectional data exchange supported. Supplies 12 VDC, 500 mA
max shared with 12 VDC Auxiliary port
Auxiliary power
1 x Auxiliary 12 VDC, 500 mA maximum shared with SPI expansion port
Communication speed
- 1200 to 115200 Bauds (automatic detection) over RS-232 and RS-485
- 10/100 Mb/s BaseT over Ethernet
Flash memory
256 MB NAND flash for application, storage and stand-alone event buffer holding 20,000
events
RAM memory
128 MB DDR2 for application loading and running
Network autonomy
Distributed data and processing
Certifications / Listing
EN50133-1, EN55022, EN60950-1, EN61000-6-1, EN61000-6-2
FCC: Part15/ICES Class A
UL 294, UL 1076, C-Tick
Note:
The KT-400 is capable of restarting automatically after total power loss and will keep the programming for more than 120
hours of power interruption. The design is using flash memory for saving access rules.
This is certified by Telefication under the requirements of EN50133-1, Recognition Class 0-3, Access Class A/B,
Environmental Class II.
wwww.EntraPASS.com
8641 S. Warhawk Rd., Conifer, CO 80433 - Tel: 303-670-1099 - Email: [email protected]