Factory Setting Menu:
The device is returned to its factory settings in this menu. The 4 digit password is prompted before entering
this menu. If the password is activated, it isn’t prompted again before entering this menu since the password
was entered before entering the main programming menu. The device returns to its factory settings when
the “
SAVE
” query is confirmed by the user while returning to the monitoring menu. Time settings, relay
operation count and relay operation time doesn’t change.
Version Information Menu:
The software and hardware versions of the device is shown in this menu.
Exit from Main Programming Menu:
This menu is used to exit from the main programming menu. The ESC button can be used for this, too. If
any changes are committed in the menus while in the main programming menu, an approval promt is
shown. If there aren’t any changes, the monitoring menu is shown directly.
Factory Settings:
Program
DIMENSIONS
CONNECTION DIAGRAM
TYP PK25
35 mm
90 mm
45 mm
62 mm
58 mm
32 mm
48 mm
35 mm
L1
N
L2
L3
Un
C1
C2
1 A1
3 2
1 A2
3 2
P11:
C2 relay will be activated everyday 20 minutes after Maghrib Salah Time and be deactivated 20
minutes before the sunrise time.
P12:
C2 relay will be activated 20 minutes before Isha’a Salah Time and be deactivated 30 minutes after
Isha’a Salah Time.
P13...P32:
Empty
Merge Function
AND-1: FREE
AND-2: FREE
Regional Settings
LANGUAGE: ENGLISH
POSITION: MECCA
TIME ZONE: 3.00
DAYLIGHT SAVING: -
H METHOD: UQM
Display Settings
CONTRAST:08
Holiday Lock
HOLIDAY-1: FREE
HOLIDAY-2: FREE
HOLIDAY-3: FREE
HOLIDAY-4: FREE
Manual Mode
RECOVRY : DISABLE
Activation Time
C1 TIME : 0
C1 SHOT : 0
C2 TIME : 0
C2 SHOT : 0
Password
PASSWORD:0000
PASSWORD STATUS:INACTIVE
P01:
C1 relay will be activated everyday 50 minutes
before Fajr Salah Time and be deactivated 10 minutes
before the sunrise time.
P02:
C1 relay will be activated 20 minutes before
every Dhuhr Salah Time except Yaumul Jumuah and
be deactivated 30 minutes after.
P03:
C1 relay will be activated 60 minutes before
every Yaumul Jumuah Salah Time and be deactivated
50 minutes after.
P04:
C1 relay will be activated everyday 20 minutes
after Asr Salah Time and be deactivated 20 minutes
before the sunrise.
P05:
C1 relay will be activated everyday 20 minutes
after Maghrib Salah Time and be deactivated 20
minutes before the sunrise time.
P06:
C1 relay will be activated everyday 20 minutes
before Isha’a Salah Time and be deactivated 30
minutes after Isha’a Salah Time.
P07:
C2 relay will be activated everyday 50 minutes
before Fajr Salah Time and be deactivated 10 minutes
before the sunrise time.
P08:
C2 relay will be activated 20 minutes before
every Dhuhr Salah Time except Yaumul Jumuah and
be deactivated 30 minutes after.
P09:
C2 relay will be activated 60 minutes before
every Yaumul Jumuah Salah Time and be deactivated
50 minutes after.
P10:
C2 relay will be activated everyday 20 minutes
after Asr Salah Time and be deactivated 20 minutes
before the sunrise.
Note: The contact resistance at
ohmic load ( eg: Incandescent
bulb,Resistance devices ) is 16A.
It is recommended to use a
contactor if the inductive load
(eg: AC motor, fluorescent,etc.)
or capacitive load (eg: Led
Drivers,UPS, Fluorescent
( Electronic Ballast), etc.) switch.
Otherwise adhesion may
occur in relay contacts.