NT PRESSURE TRANSDUCER MODELS 4100, 4210

11

Entegris, Inc.   |   User Guide   

Certifications

            CE COMPLIANCE

Entegris products have been tested  
to various test standards required  
by the EMC 2104 /30 /EU directive. 
The results of this testing are on  
file at Entegris and are available  
upon request. 

Please contact the factory for  
the latest information. The most 
current specifications may be  
found on Entegris’ Web site at: 

http://www.entegrisfluidhandling.
com/Product.aspx?G=1613

 

CLASS I DIVISION 2  

HAZARDOUS ENVIRONMENTS

Entegris has tested our standard 
products to the UL 61010-1,  
ANSI/ISA  12.12.01 standards for  
use in Class I, Division 2 Group A–D, 
T6 10°C ≤Ta ≤65°C hazardous 
environments. The results of this 
testing are on file at Entegris and  
are available upon request. 

All spec i fications are subject to 
change. Please contact the factory  
for the latest information.

Summary of Contents for 4000 Series

Page 1: ...P N 01 1027289 REV A 04 17 NT Pressure Transducer Models 4100 4210 User Guide ...

Page 2: ...ure Requirements 6 Pressure Limits 7 Pressure Reference Accuracy 7 Linear Output Signal 8 Troubleshooting 9 Reference 10 Physical Specifications 10 Electrical Specifications 10 Performance Specifications 10 Certifications 11 CE Compliance 11 Class I Division 2 Hazardous Environments 11 Ordering Information 12 Model 4100 Single port 12 Model 4210 Flow through 13 Installation Drawings 14 Model 4100 ...

Page 3: ... high purity inert materials WARNING Attempting to install or operate standard NT 4000 Series Pressure Transducers without reviewing the instruc tions contained in this manual could result in personal injury or equipment damage Polypropylene electrical connector option Signal conditioning circuit Electronic pressure sensor Process connection PTFE body Cut away Example NT Single port Pressure Trans...

Page 4: ...flare and assembly procedure at www entegrisfluidhandling com follow the Fittings Tube Fittings Flaretek Tube Fittings links When installing flared tubing to the pressure transducer the flared tube is pushed over the transducer s fitting until the fitting reaches the smaller tube diameter The amount of torque required to tighten the coupling nut is dependent upon the size of the fitting Fitting si...

Page 5: ...lean power and must be used only to power similar measurement type devices The power supply must not be used to power inductive loads such as motors relays or solenoids These devices may produce transients that may affect the pressure transducer measurements when the inductive device is powered up or powered down NOTE Be sure to ground the shield of the cable to local ground 24 VDC Pressure transd...

Page 6: ...ter where maximum load resistance ohms power supply voltage volts meter resistance ohms theoretically 0 VPS VPS 12 V 20 mA WARNINGS WARNING For use in Class I Division 2 Hazardous Environ ments models with disconnecting cable options must be wired in accordance with the control drawing 01 1033562 on page 17 WARNING Do not remove or replace while circuit is live unless the area is known to be free ...

Page 7: ... and should not be tampered with or opened Opening the cover shall void the product warranty WARNING Any attempt to remove or tamper with the transducer cover will void the warranty and damage the unit PRESSURE AND TEMPERATURE REQUIREMENTS The minimum pressure required is atmospheric pressure The pres sure transducer may be damaged if subjected to vacuum pressure pressure that is less than atmo sp...

Page 8: ... limited by the fitting Consult the fitting specification for maximum over pressure limits WARNING The pressure limits for standard NT Pressure Trans ducers 4000 Series decrease significantly for temperatures above 65 C 149 F Exceeding these limits may result in personal injury or equipment damage PRESSURE REFERENCE ACCURACY The accuracy of the pressure transducer output is 1 of full scale This ac...

Page 9: ...nc LINEAR OUTPUT SIGNAL The output signal of the pressure transducer is a linear function proportional to the applied pressure Full scale 4 mA 0 psig Pressure Measurement Full scale 0 psig Pressure Measurement Current Output mA Voltage Output V 20 mA 10 V or 5 V 0V ...

Page 10: ...l of the pressure transducer with a battery powered current voltage meter The meter may be placed in series with the pressure transducer to measure the current output or it may be used to directly measure the voltage output Using the battery powered current volt meter is an effective method to determine whether the device or the on site data acquisition system is not functioning properly ...

Page 11: ...z Nonwetted parts Polypropylene polyethylene Viton PVDF in addition to materials listed above Connection type Flaretek tube fitting Super 300 Type Pillar tube fitting NPT PrimeLock available upon request Electrical Specifications Input voltage 24 VDC 12 30 VDC Input current 20 mA maximum Pressure signal output ranges 4 20 mA 0 5 VDC 0 10 VDC Electrical connection 6 12 30 FEP jacketed pigtail or po...

Page 12: ...information The most current specifications may be found on Entegris Web site at http www entegrisfluidhandling com Product aspx G 1613 CLASS I DIVISION 2 HAZARDOUS ENVIRONMENTS Entegris has tested our standard products to the UL 61010 1 ANSI ISA 12 12 01 standards for use in Class I Division 2 Group A D T6 10 C Ta 65 C hazardous environments The results of this testing are on file at Entegris and...

Page 13: ... 1 2 FNPT M02 1 4 MNPT Electrical connector types B06 FEP jacketed 6 pigtail electrical cable B12 FEP jacketed 12 pigtail electrical cable B30 FEP jacketed 30 pigtail electrical cable D00 Polypropylene connector cable not included D06 Polypropylene connector and 6 PVC cable D12 Polypropylene connector and 12 PVC cable D30 Polypropylene connector and 30 PVC cable Primary secondary seal U3 Kalrez 63...

Page 14: ...per 300 Type Pillar tube fitting W06 3 4 Super 300 Type Pillar tube fitting W08 1 Super 300 Type Pillar tube fitting Electrical connector types B06 FEP jacketed 6 pigtail electrical cable B12 FEP jacketed 12 pigtail electrical cable B30 FEP jacketed 30 pigtail electrical cable D00 Polypropylene connector cable not included D06 Polypropylene connector and 6 PVC cable D12 Polypropylene connector and...

Page 15: ...Super 300 Type Pillar tube fitting 76 2 mm 3 00 11 0 mm 0 43 3 8 Super 300 Type Pillar tube fitting 76 2 mm 3 00 15 0 mm 0 59 1 2 Super 300 Type Pillar tube fitting 76 2 mm 3 00 17 5 mm 0 69 Side View Side View Side View Flaretek Connection 10 7 mm 0 42 A B 3 conductor FEP jacketed pigtail connection BXX Cable length up to 30 feet 25 4 mm 1 00 Ø47 8 mm 1 88 Ø47 8 mm 1 88 Super 300 Type Pillar Conn...

Page 16: ... fitting 96 0 mm 3 78 102 4 mm 4 03 21 6 mm 0 85 3 4 Flaretek tube fitting 104 1 mm 4 10 108 5 mm 4 27 25 4 mm 1 00 1 Flaretek tube fitting 112 5 mm 4 43 120 7 mm 4 75 30 5 mm 1 20 Note No NPT option on Model 4210 Side View Top View Flaretek Connection 10 7 mm 0 42 A B Receptacle with connector removed 8 4 mm 0 33 3 conductor pigtail connection BXX Cable length up to 30 feet 3 conductor connector ...

Page 17: ... Pillar tube fitting 96 0 mm 3 78 79 5 mm 3 13 21 6 mm 0 85 3 4 Super 300 Type Pillar tube fitting 104 4 mm 4 11 88 4mm 3 48 25 7 mm 1 01 1 Super 300 Type Pillar tube fitting 111 8 mm 4 40 98 6mm 3 88 29 7 mm 1 17 Side View Top View Super 300 Type Pillar Connection 10 7 mm 0 42 A B 8 4 mm 0 33 25 4 mm 1 00 76 2 mm 3 00 C 44 5 mm 1 75 Ø47 mm 1 85 3 conductor connector cable DXX Cable length up to 3...

Page 18: ...ure Output Table 2 Entity Parameters for Models 4100 4210 with Voltage Output See Note 2 Signals Vmax VDC Imax mA Ci nF Li mH Red Black 30 150 0 0 0 48 Brown Blue A00 DXX Cable Options PXX TXX Cable Options Cable Option Conductor Color Transducer 4 20mA Output Pressure Transducer Voltage Output 2 For use in Class I Division 2 Groups A B C D the following pressure transducer models must be used wit...

Page 19: ...Entity parameters for Models NT4100 NT4200 with voltage output see note 2 Cable option conductor color A00 DXX cable option Red and black Signals Power and ground Vmax 30 VDC Imax 150 mA Pi 2 25 W Ci 0 48 nF Li 0 0 mH Table 3 Nonincendive field wiring apparatus vs associated nonincendive field wiring apparatus requirements NONINCENDIVE FIELD WIRING APPARATUS MODEL NT4100 4200 RELATIONSHIP ASSOCIAT...

Page 20: ...XX A00 A XX XX 4210 XXXX XXX DXX A XX XX 2 For use in Class I Division 2 Groups A B C D the following pressure transducer models must be used with an approved associated nonincendive field wiring apparatus that meets the requirements in Table 3 with the entity parameters in Table 2 4100 XXXX XXX A00 B XX XX 4100 XXXX XXX DXX B XX XX 4100 XXXX XXX XXX B XX XX PXX 4100 XXXX XXX A00 C XX XX 4100 XXXX...

Page 21: ...Entegris Inc General Limited Warranty To view and print this information visit entegris com and select the Legal Trademark Notices link in the footer Entegris does not warranty any failure in the case of customers using unapproved foreign components Tel 1 952 556 4181 Fax 1 952 556 8022 Toll Free 800 394 4083 Customer Service 129 Concord Road Billerica MA 01821 USA Corporate Headquarters Entegris ...

Reviews: