10.
Manual Bypass Operation
(Switching from ONLINE to BYPASS)
*Used only when External Manual Bypass switch is installed.
UPS configurations
1.
Various settings that have been chosen are shown in the UPS setting display.
2.
To enter configuration mode, press the button for one second. The first configuration
parameter (Output Volt Setting) will be shown on the LCD display.
3.
Press the button to scroll through the parameters and stop at parameter (Manual
Bypass)
4.
Press the
button to select the parameter (Manual Bypass).
5.
You will see factory default (Off).
6.
Press the button to scroll through the options for Manual Bypass till you see option
(On).
7.
Press the button to select the option (On).
8.
You may be prompted to save the selection, if so press the button to either confirm
or save your selection. Other options are saved and started automatically. See the table
below for further details.
9.
If no buttons are pressed (or user inactivity) for ten seconds, the UPS shall exit the
configuration mode and return to normal mode displaying Line mode.
10.
After switching to Manual Bypass, you will see Manual Bypass on the LCD display.
11.
After verifying the UPS in on Manual Bypass, switch the external manual bypass switch
to BYPASS mode.
12.
After switching the external manual bypass switch to BYPASS mode, you will see the red
light on the external bypass box. The UPS is now on BYPASS mode.
Caution!
The factory default settings do not necessarily have to be changed, although you are free to tailor the
UPS to your specific needs.