![Enplus Evo UPS 1000VA User Manual Download Page 37](http://html.mh-extra.com/html/enplus/evo-ups-1000va/evo-ups-1000va_user-manual_2414039037.webp)
37
ENVIRONMENTAL
Ambient temperature:
+0 °C to +40 °C
Recommended temperature:
+15 °C to +25 °C
Storage temperature:
-15 °C to +50 °C
Cooling:
Forced air-cooling
Humidity:
0-95%, non-condensing
Audible noise:
< 45 db normal and battery mode (1000 VA)
< 50 db normal and battery mode (2000-3000 VA)
STANDARDS
Safety:
EN50091-1,
EN62040-1-1, IEC62040-1-1, UL1778
Emissions:
EN50091-2,
EN62040-2 / IEC62040-2
Immunity:
EN50091-2, FCC Class B (1000VA)
EN50091-2, FCC Class A (2000/3000VA)
EN62040-2 Category C1 (1000VA)
EN62040-2 Category C2 (2000/3000VA)
HV Tower Model at P.F 0.8
OUTPUT POWER 1000VA/800W
2000VA/1600W
3000VA/2400W
Connection Input
IEC 320 (10A)
IEC 320 (10A)
IEC 320 (16A)
Connection Output
4 x IEC 320 (10A)
8 x IEC 320 (10A),
1 x IEC 320 (16A)
8 x IEC 320 (10A),
1 x IEC 320 (16A)
4 x 5-15R (US)
12 x 5-15R (US)
12 x 5-15R (US)
2 x Europe
6 x Europe,
1 x IEC 320 (16A)
6 x Europe,
1 x IEC 320 (16A)
Battery type
Lead-acid 7AH/12V
Lead-acid 7AH/12V
Lead-acid 7AH/12V
Number of batteries 3
6
8
Backup time/
full load
3
~5 min
3
~5 min
3~4 min
Recharge time
<4 hours to 90%
<4 hours to 90%
<4 hours to 90%
Dimensions
W x D x H mm
152 x 420 x 238
225 x 420 x 358
225 x 420 x 358
Net Weight kg
16.2
31.1
33.6