Cover and energize the system

*

 

WARNING: 

Before energizing, make sure that all IQ Batteries in the 

system are properly installed and conductors terminated.

NOTE: 

Check the box for updates on cover installation instructions.

A )  Check that the 

field wiring compartment

 cover(s) for all IQ Batteries in 

the system are closed and secured.

+

 

DANGER:

 

Risk of electric shock

. Before continuing, check that IQ 

Battery units are properly wired, and ground connection does not have a 

L1 or L2 connection, as this introduces a safety hazard. 

•  Apply AC power to the IQ Battery circuits. Do NOT turn On the DC switch on 

IQ Batteries. 

•  Using a voltmeter measure the IQ Battery chassis metal to ground (e.g., 

grounded conduit) and ensure there is no AC voltage source present. If 

wiring is incorrect, a ground fault may exist, and the AC voltage may read 

~120VAC. If voltage is present, DO NOT touch the chassis, and immediately 

remove AC power from the IQ Battery circuits. 

•  Remove AC power to the IQ Battery circuits and correct the wiring. 

*

 

WARNING: 

Before commissioning, DC Switch on IQ Battery shall 

not be turned on, unless instructed in Enphase Installer App. Turning DC 

switch On before it is instructed in Enphase Installer App can damage 

IQ Battery.

B )  Connect the AC power (branch circuit protection On) to IQ Battery and 

commission the IQ Battery using Enphase Installer App with DC switch 

in Off position. Wait for Envoy to update the IQ Battery firmware. Turn DC 

switch On only after you see a message in Enphase Installer App asking 

to turn it On.

      

*

 

WARNING: 

After commissioning, always follow the sequence to supply 

the AC power first and then turn the DC Switch On. The turn Off sequence for 

AC power or DC Switch does not matter.

        NOTE: 

Do NOT leave the IQ Battery unit’s DC switch in the On position for 

any extended period of time (such as overnight or for more than 24 hours) 

unless IQ Battery is commissioned (communicating with Envoy), connected 

to AC, and has passed functional testing and is operational. Leaving the DC 

switch On without AC connection and communication with the system will 

drain the battery and may cause damage to the battery cells such that they no 

longer be able to charge. Damage resulting from this improper installation and 

misuse is not covered under the product’s limited warranty.

C )  Place enclosure cover(s) over the battery(ies) as follows.

IQ Battery 3 (single-width battery cover)

•  Pick up the IQ Battery 3 Battery cover, stand in front of the battery so that 

the cover and battery are on a level, and slide the cover over the battery 

so that the interior guides of the cover slide easily over the guides on the 

battery unit. 

•  Check that the screw hole on top of the battery cover aligns with that on the 

battery. 

•  Use the included screw to attach the cover to the battery. Tighten the screw 

as needed.

IQ Battery 10 (triple-width battery cover) 

•  The IQ Battery 10 Battery cover in wide and may require two persons to 

guide smoothly over the battery units. 

•  Pick up the IQ Battery 10 Battery cover, stand in front of the battery so that 

the cover and battery are on a level, and slide the cover over the battery 

so that the interior guides of the cover slide easily over the guides on the 

battery units. 

•  Check that the screw holes on top of the battery cover align with those on 

the batteries. 

•  Use the included screws to attach the cover to the batteries. Tighten the 

screws as needed.

8

IQ Battery 10 without cover

A )  Use the Enphase Installer App to commission the IQ Battery(ies). 

Once connected to the IQ Gateway, refer to the Enphase Installer 

App help topics for more information.

B )   After the IQ Gateway has detected the IQ Battery(ies), the IQ Battery 

LEDs operate as described in the following section.

CONFIGURE and ACTIVATE

OPERATION

a

 

LED overview

After being commissioned, the LED flashes yellow while each IQ Battery 

boots up. If the LED rapidly flashes green for more than two minutes, 

the battery is in trickle charge mode and will remain so until it reaches 

a minimum state of charge (up to 30 minutes). After the IQ Battery is 

booted up, the LED becomes blue or green depending on the charge 

level. If the LED flashes yellow after one hour or changes to a flashing 

red state, contact Enphase Customer Support at 

enphase.com/en-us/

support/contact.

State

Description

Uncommissioned

Flashing blue

After booting up, when IQ Battery has paired 

with an IQ Gateway but has not passed the 

commissioning three-way handshake to 

confirm that it is an Enphase device.

Flashing green

After passing the three-way handshake with 

the IQ Gateway.

After commissioning (normal operation)*

Rapidly flashing yellow

Starting up / Establishing communications

Red flashes in sequences of 2

Error. See “Troubleshooting”.

Solid yellow

Not operating due to high temperature. See 

“Troubleshooting”.

Solid blue or green

Idle. Color transitions from blue to green as 

state of charge increases. You can check 

Enphase Installer Platform for charge status.

Slowly flashing blue

Discharging

Slowly flashing green

Charging

Slowly flashing yellow

Sleep mode activated

Off

Not operating. See “Troubleshooting”.

* IQ Battery batteries have a one-hour orphan timer. If the IQ Gateway stops 

communicating with them, after one hour the IQ Battery batteries return to an 

“uncommissioned” state. 

b

 

Troubleshooting

If the IQ Battery(ies) are not operating correctly, perform the following 

steps. If the issue persists, contact Enphase Customer Support at 

enphase.com/en-us/support/contact

.

A )  If the IQ Battery(ies) do not operate, check the temperature in the 

room and increase cooling and/or ventilation as required. Check 

that the front, top, and sides of the IQ Battery batteries have at 

least 15cm (six inches) of unobstructed clearance.

B )  If the IQ Battery LED is off, turn off the breaker for the branch 

circuit, wait for at least one minute, and turn it back on.

 NOTE

: During a brownout or blackout, the IQ Battery powers down 

automatically. This is normal. When power is restored, it automati-

cally starts up again.

C )  If you do not see IQ Battery information in Enphase Installer 

Platform, check that the IQ Gateway and the Internet connection 

are working. If the issue persists, contact Enphase Customer 

Support at 

enphase.com/en-us/support/contact

.

64

m

m

1036 mm

287 mm

345 mm

Limitation of Use :

Your IQ Battery unit is not intended for use as a primary or backup power 

source for life-support systems, other medical equipment, or any other use 

where product failure could lead to injury, loss of life, or catastrophic prop-

erty damage. Enphase disclaims any and all liability arising out of any such 

use of your IQ Battery unit. Further, Enphase reserves the right to refuse to 

provide support in connection with any such use and disclaims any and all 

liability arising out of Enphase’s provision of, or refusal to provide, support 

for your IQ Battery device in such circumstances.

Summary of Contents for ENCHARGE-3-1P-NA

Page 1: ...guration for back up of the entire main load panel This configuration supports up to an 80A breaker for the PV circuit and an 80A breaker for battery storage Whole home backup with IQ System Controller as service entrance and PV combiner connected to main load panel This is the preferred configuration when you back up the entire main load panel and the size of the PV combiner circuit is more than ...

Page 2: ...t screwdriver socket wrench torque wrench level wire stripper and stud finder if installing on studs Fasteners for wall mount bracket Slots are 6 8mm 0 27 Check with a structural engineer and local standards for requirements Single wide bracket Three 1 4 lag bolts or screws 7 6 cm 3 inches long depending on attachment wall Triple wide bracket Nine 1 4 lag bolts or screws 7 6 cm 3 inches long depen...

Page 3: ...ction circuit The subpanel could be a small two circuit box with circuit breakers The circuit breakers in the box would have to be suitable for back feeding per NEC 408 36 D Select the right size subpanel and breakers based on the number of IQ Battery units being installed Up to four IQ Battery 10s or twelve IQ Battery 3s can be safely connected to 80A load center To do this you must purchase an o...

Page 4: ... mounting holes on the left and right align with the adjacent studs B Use a level to keep the bottom of the wall mount bracket level C Use 1 4 screws or masonry attachments for masonry to attach the bracket using one screw and washer for each slot 6 8mm 0 27 Use screws in each section of the mounting bracket to support the three IQ Battery units There is an array of slots so that you can choose th...

Page 5: ...J Use a Phillips screw driver to loosen the screws securing the field wiring compartment cover and remove the cover Keep the cover and screws handy as you will need them later K Attach the battery to the mounting bracket aligning the screw hole at the top of the battery with the screw hole at the top of the bracket L To record the installation of each IQ Battery base unit scan the serial number la...

Page 6: ...to its correspond ing conductor Lines and Ground Each terminal accepts two 14 8 AWG conductors 11mm 7 16 inch strip length Tighten to 14 lb in G If installing an IQ Battery 10 route the wires from the first IQ Battery to the adjacent IQ Battery through the inter unit raceway There are two positions for each line and for ground in the terminal block to allow for daisy chaining WARNING Risk of equip...

Page 7: ...crews to attach the cover to the batteries Tighten the screws as needed 8 IQ Battery 10 without cover A Use the Enphase Installer App to commission the IQ Battery ies Once connected to the IQ Gateway refer to the Enphase Installer App help topics for more information B After the IQ Gateway has detected the IQ Battery ies the IQ Battery LEDs operate as described in the following section CONFIGURE a...

Page 8: ... the IQ Battery ies in storage ensure that AC power is not present and that the DC switch is in the Locked position While in storage damage to the battery can occur from over discharge If the battery state of charge falls to 0 the IQ Battery ies can be damaged or destroyed Because of this the IQ Battery ies must only be stored for a limited amount of time The IQ Battery ies must be installed and e...

Reviews: