WIRING INSTRUCTIONS (Hardwired LCS)

Route the LCS conduit to a nearby service panel or junction box. Use the 

included ¼” trade size watertight fitting to provide a moisture-resistant seal 

with the service panel or junction box. If necessary, drill a 1/2” diameter hole to 

accommodate the liquid-tight fitting or use the included 1/4” NPT to 1/2” NPT  

thread reducer kit.

Figure 8: Wiring the LCS 
in a Junction Box

NOTE: 

The three LCS service conductors 

use stranded 12AWG, 75ºC copper wire. The 

insulation of each conductor is color coded for 

standard 240V AC installation:
 

Green:  Ground

 

Black:  Line 1  (120V AC to Ground)

 

Red:       Line 2  (120V AC to Ground)

REMARQUE:

 Les trois conducteurs service 

la LCS utiliser multibrins 12 AWG, 75ºC fil de 

cuivre. L’isolation de chaque conducteur est un 
code couleur pour une installation standard de 

240 VAC:
 

Vert: 

Mise à la Terre

 

Noir:  Ligne 1 (120VAC à Mise à la Terre)

 

Rouge:   Ligne 2 (120VAC à Mise à la Terre)

NOTA:

 Los tres conductores de servicio EVSE 

utilizan cable de cobre trenzado de 10 AWG 

y 75ºC. El aislamiento de cada conductor 

está codificado por colores para la instalación 

estándar de 240 V CA:
                Verde:   Tierra

                Negro:   Línea 1 (120V CA a tierra)

                Rojo:     Línea 2 (120V CA a tierra)

NOTE: 

Before connecting the LCS service 

conductors, please carefully read the section 

of this manual titled Service Connections on 

page 15. If you are unsure of the type of power 

provided at the service panel, please consult 

with your local utility or call your Service 
Representative for assistance.

Summary of Contents for ClipperCreek LCS

Page 1: ... Model LCS User Manual A division of Enphase Energy Inc ...

Page 2: ...hts reserved Printed in the USA Manual Number 7004 0013 B WARNING This product can expose you to chemicals including Carbon Black which is known to the State of California to cause cancer For more information go to www P65Warnings ca gov ADVERTENCIA Este producto puede exponerte a químicos incluso Negro Carbón que se conocido por el Estado de California como causante de cáncer Para más información...

Page 3: ...CEDURES 21 LCS EVSE Mounting for Hollow Wall Construction 22 LCS EVSE Mounting for Solid Wall Construction 23 MOUNTINGTHE SAE J1772 LCS CONNECTOR HOLSTER 24 WIRING INSTRUCTIONS Hardwired LCS 25 RECEPTACLE INSTRUCTIONS Plug In LCS P 26 CHARGE CABLE WRAP GUIDELINES 27 GROUNDING INSTRUCTIONS 28 LCS Hardwired EVSE Grounding 28 LCS P Plug in EVSE Grounding 28 MOVING STORAGE INSTRUCTIONS 29 MAINTENANCE ...

Page 4: ... 19 5 Mounting the LCS to Hollow Wall 22 6 Mounting the LCS to a Solid Wall 23 7 Mounting the LCS Connector Holster using Exterior Wood Screws and Washers 24 8 Wiring the LCS in a Junction Box 25 9 Preferred Orientation of the NEMA Receptacles above the LCS P 26 10 Drape the Charge Cable Loosely around the LCS Enclosure 27 Tables 1 Front Panel LED Information 14 2 LCS Configurations 15 ...

Page 5: ...ire quelque chose qui pourrait causer des dommages à l équipement ATENCIÓN Este símbolo significa tener cuidado Usted es capaz de hacer algo que puede resultar en daños al equipo WARNING This symbol means danger This is a situation that could cause bodily injury Before working on any electrical equipment be aware of the hazards involved with electrical circuitry and standard practices for preventi...

Page 6: ...OMMERCIAL GARAGE is defined as a facility or portion thereof used for the repair of internal combustion vehicles in which the area may be classified due to flammable vapors being present such as from gasoline Do not place fingers inside of the coupler end of the SAE J1772charge cable Do not allow children to operate this device Adult supervision is mandatory when children are in proximity to an EV...

Page 7: ...e si elles sont physiquement ouverte fissuré effiloché ou autrement visiblement endommagé Contactez votre représentant du service pour service immédiatement Consultez la section Support à la clientèle dans ce manuel pour obtenir des informations sur le représentant du service dans votre région Ne pas utiliser dans les garages commerciaux où un garage commercial est défini comme une installation ou...

Page 8: ...orme aux exigences de la réglementation locale avant de raccorder l EVSE Ne pas utiliser cet EVSE avec une rallonge ou adaptateur de prise murale Branchez cet EVSE directement dans le réceptacle S assurer que l EVSE est fixé au mur ou placé sur un support afin qu il ne soit pas suspendu à l installation électrique Le réceptacle n est pas conçue pour supporter le poids de l EVSE Instrucciones Perti...

Page 9: ...tán específicamente diseñados para reubicaciones ocasionales como la mudanza de una casa a otra Por su seguridad personal el interruptor de circuito DEBE estar apagado antes de enchufar Y O desenchufar dispositivos de 240V incluyendo este dispositivo EVSE Se recomienda encarecidamente una salida receptáculo NEMA dedicada EL receptáculo NEMA se desgastan con el tiempo especialmente cuando se produc...

Page 10: ...require an external ventilation system to prevent the accumulation of hazardous or explosive gases when charging indoors Consult the vehicle owner s manual to determine if your vehicle requires ventilation during indoor charging REMARQUE VENTILATION Certains véhicules électriques requiert un système de ventilation externe afin de prévenir l accumulation de gaz dangereux ou explosifs lors de charge...

Page 11: ...res No cargue el vehículo con el LCS si se requiere ventilación CAUTION DO NOT CHARGE a vehicle indoors if it requires ventilation Contact your Service Representative for information ATTENTION NE PAS RECHARGER un véhicule à l intérieur si il nécessite une ventilation Contactez votre représentant de service pour plus d informations ATENCIÓN NO RECARGUE un vehículo en interiores si requiere ventilac...

Page 12: ...nt etc could affect operation If interference to the EVSE is suspected we suggest the following steps be taken before consulting your ClipperCreek Sales and Service Representative for assistance 1 Reorient or relocate nearby electrical appliances or equipment during charging 2 Turn off nearby electrical appliances or equipment during charging CAUTION Changes or modifications to this product by oth...

Page 13: ...e using a special communication line in the cable Within a few seconds the green Charging light on the face of the LCS will turn on and the charging cycle will begin After an average driving day the vehicle battery pack will require several hours to recharge completely Charging overnight is the most convenient way to maintain healthy batteries and ensure the vehicle s full range will be available ...

Page 14: ...LCS is unable to communicate with the vehicle correctly or a safety fault condition has been detected by the unit Table 1 Front Panel LED Information Amber Power LED Green Charging LED Red Power Fault LED Red Charging Fault LED Fault Condition No power to EVSE Check circuit breaker off off off off 1 2 3 4 5 6 7 ON ON ON ON ON ON off off off ON ON not blinking off off off off off off ON not blinkin...

Page 15: ...ired 15A n a LCS 20 Hardwired 20A n a LCS 20P NEMA 14 30P 30A NEMA 14 30R LCS 20P NEMA 6 50P 40 50A NEMA 6 50R LCS 20P NEMA 14 50P 40 50A NEMA 14 50R LCS 25 Hardwired 25A n a LCS 25P NEMA 14 30P 30A NEMA 14 30R LCS 25P NEMA 6 50P 40 50A NEMA 6 50R LCS 25P NEMA 14 50P 40 50A NEMA 14 50R LCS 30 Hardwired 30A n a LCS 30P NEMA 14 30P 30A NEMA 14 30R LCS 30P NEMA 6 50P 40 50A NEMA 6 50R LCS 30P NEMA 14...

Page 16: ...ión a Tierra debe conectarse al punto Neutro en un solo punto general mente en la entrada de servicio del panel de interruptores automáticos CAUTION If a 240V 3 phase feed is from a Delta connected secondary the leg used must have a center tap That tap must be Grounded Only the two phases either side of the center tapped leg can be used See Figure 4 ATTENTION Si une alimentation à triphasé 240V pr...

Page 17: ...r outputs correspond to the same inputs on the LCS Also each of the two 3 phase diagrams shows an L3 output which is not used Do not connect all three phases of a 3 phase secondary to the LCS This is a single phase device The Neutral at the service panel must be connected to Earth Ground somewhere in the system on any of the three connection arrangements Ground fault protection is not possible unl...

Page 18: ...s peut être utilisé pour fournir 208V à la LCS Par exemple L1 L2 ou L1 L3 ou L2 L3 Laissez la borne inutilisée ouverte Ne le connectez pas à un bar Neutre ou à la Mise à la Terre Assurez vous que le point central est Mis à la Terre quelque part dans le système NOTA Con un secundario conectado en Y cualquiera de las dos piernas puede ser utilizada para proporcionar 208V a la LCS Por ejemplo L1 y L2...

Page 19: ...3 du delta est 208V par rapport à la position Neutre et il est parfois désigné comme un stinger Ne pas utiliser ce troisième ligne Consultez la documentation du transformateur fabricant pour être sûr du borne unique peut fournir la puissance requise ATENCIÓN Con la conexión Delta una pierna debe ser de derivación central Sólo las dos fases en cualquier lado de la derivación central puede ser utili...

Page 20: ...s être utilisé avec la LCS Aucun point Neutre est disponible pour être connecté à Mise à la Terre pour protection de défaut à la terre Le LCS ne permettra pas le contacteur de fermer si elle ne détecte pas la présence d un fil de Masse connecté à un point Neutre sur le secondaire du transformateur ATENCIÓN Un transformador trifásico secundario de conexión delta sin derivación central en una pierna...

Page 21: ...tall rectangular pattern Use a template to mark hole locations on the wall WARNING For safety always turn off input power to the EVSE at the circuit breaker panel prior to plugging it in or wiring it to the service lines Likewise turn off the circuit breaker prior to unplugging it or disconnecting the unit from the service lines AVERTISSEMENT Pour sécurité toujours désactiver le courant d entrée d...

Page 22: ...ut preferably all four mounting holes can take advantage of solid structural framing inside of the wall or a strong wall surface such as plywood For any remaining mounting holes which do not have a solid mounting structure such as drywall without a solid backing it will be necessary to use proper anchoring hardware such as drywall toggles or molly bolts ...

Page 23: ...drill appropriately sized holes and use multi set or wedge anchor hardware at all four mounting points Machine screw size 10 hardware is recommended for mounting the LCS Screw shafts of at least 2 are recommended The LCS mounting holes are 3 16 in diameter so ensure that the screw heads do not exceed this size Place appropriately sized washers between the screw heads and the LCS enclosure mounting...

Page 24: ...ounting surface The vertical alignment of the LCS and SAE J1772 connector holster mounting holes allows for the convenient mounting of both components onto the same post or wall structure For example the holster may be mounted directly above the LCS Place the SAE J1772 connector holster such that both mounting holes can take advantage of solid structural framing inside of the wall or a strong wall...

Page 25: ...Ground REMARQUE Les trois conducteurs service la LCS utiliser multibrins 12 AWG 75ºC fil de cuivre L isolation de chaque conducteur est un code couleur pour une installation standard de 240 VAC Vert Mise à la Terre Noir Ligne 1 120V ACàMiseàlaTerre Rouge Ligne 2 120V ACàMiseàlaTerre NOTA Los tres conductores de servicio EVSE utilizan cable de cobre trenzado de 10 AWG y 75ºC El aislamiento de cada ...

Page 26: ... to a maximum of 12 inches in length For this reason the LCS P must be mounted below the NEMA receptacle and must also be located within 12 inches of it The ground pin is located at the top position of the plug With this in mind it is recommended that the receptacle be oriented accordingly such that the ground socket is at the highest point Figure 9 Preferred Orientation of the NEMA Receptacles ab...

Page 27: ...mber of wires coiling the charge cable too tightly around the LCS enclosure will result in the charge cable feeling warmer to the touch than would ordinarily be the case To minimize this effect it is recommended that the charge cable be loosely draped around the LCS enclosure body with larger loops This will also permit greater convenience in pulling off additional loops if a longer charge cable r...

Page 28: ... the equipment grounding conductor may result in a risk of electric shock Check with a qualified electrician if doubt exists as to whether the product is properly grounded Do not modify the plug provided with the product if it will not fit the outlet have a proper outlet installed by a qualified electrician AVERTISSEMENT Une mauvaise connexion du conducteur de terre peut entraîner un risque de cho...

Page 29: ...ior to hard wiring an LCS to or disconnecting an LCS from the service lines Likewise always turn off input power to the EVSE at the circuit breaker panel prior to plugging an LCS P into or unplugging an LCS P from a NEMA socket When transporting the EVSE do not lift or carry the entire unit by the SAE J1772 charge cord Likewise do not lift or carry the entire unit by the flexible conduit and input...

Page 30: ...onnecteur de charge EV 1 Eteignez la équipement au disjoncteur avant de le nettoyer 2 Débranchez l EVSE du recopérable 3 Nettoyez l équipement à l aide d un chiffon doux légèrement humidifié avec une solution de détergent doux Ne jamais utiliser de tampons abrasifs de poudre à récurer ou de solvants inflammables tels que l alcool ou le benzène ADVERTENCIA Para reducir el riesgo de descarga eléctri...

Page 31: ...h of cable LCS 25 and LCS 30 weighs approx 2 9 kg 6 4 lbs with SAE J1772 connector and 25 length of cable LCS 20P weighs approx 2 5 kg 5 6 lbs with SAE J1772 connector and 25 length of cable LCS 25P and LCS 30P weighs approx 3 0 kg 6 6 lbs with SAE J1772 connector and 25 length of cable Environment Operating Temperature 30 C to 50 C 22 F to 122 F Storage Temperature 40 C to 80 C 40 F to 176 F Encl...

Page 32: ...tion is printed on the label on the side of the LCS enclosure If your call is made after business hours or on weekends please leave your name telephone number the unit serial number and a brief description of the problem A Service Representative will call back at the earliest opportunity Distributor Service Number Here To contact ClipperCreek directly for service call 877 694 4194 Monday Friday 8a...

Page 33: ...ncluding but not limited to improper connections with peripherals external electrical faults accident disaster misuse abuse or modifications to the product not approved in writing by Enphase Any service repair outside the scope of this limited warranty shall be at applicable rates and terms then in effect This warranty covers factory parts and factory labor only it does not cover field service or ...

Page 34: ...LCS User Manual Page 34 This page is intentionally blank ...

Page 35: ...LCS User Manual Page 35 This page is intentionally blank ...

Page 36: ...www clippercreek com 877 694 4194 ClipperCreek A division of Enphase Energy Inc ...

Reviews: