A)  Make sure that the main load center wires are de-energized until you 

have secured the CT wires in the terminal blocks.

B)  Before running the CT wires through the conduit, use colored tape to 

mark one of the CTs and the free end of its wires.

C)  For the marked CT wires, connect the white wire to “IA•” and the blue 

wire to “IA”.

D)  For the unmarked CT wires, connect the white wire to “IB•” and the blue 

wire to “IB”.

E)  Tighten all connections to 5 in-lbs.
F)  Clamp the marked CT on the load center feed wire Line 1 (matching 

the Envoy’s “A” voltage terminal) 

with the CT arrow pointing toward the 

load (away from the grid).

G)  Clamp the unmarked CT on the load center feed wire Line 2 (matching 

the Envoy’s “B” voltage terminal) with the CT arrow pointing toward the 
load (away from the grid).

      Install CTs for Consumption Metering (optional)

The Envoy-S inside the AC Combiner Box is pre-wired at the terminal blocks for power and production metering connections. One solid-core current transformer 
(CT) is provided for revenue grade production metering. You can install two optional split-core CTs to provide consumption metering. To do this, you must create 
a protected route using conduit for the CT wires from the main load center to the Envoy-S. If you need to extend the wires, refer to the 

Enphase Envoy-S Installation 

and Operation Manual 

at: 

enphase.com/support.

7

Note

Because of variance in load center design and main power feed, there may not always be enough space to install consumption metering CTs.

DANGER! 

Risk of electrocution! Do not install CTs when cur-

rent is flowing in the sensed circuit. Always install CT wires 

in the terminal blocks before energizing the sensed circuit.

Envoy-S Terminal Block

Load Center

To Grid

Consumption

CTs

white

white blue

blue

A

B

N

C

IA●

IA

IB●

IB

IC●

IC

IA●

IA

IB●

IB

IC●

IC

1

2

3

4

NO

REF CMN

5

C

CMN

Production

Consumption

Relay

Digital Input

CU, 14 AWG, 75C

MEAS CAT III

OVC III

PD, B300

OVC II

 



From AC Combiner

DANGER!  

Risk of electric shock. Always de-energize the load center 

before beginning wiring.

Notes

It is important to match CT and sense voltage phases. To properly 

measure power and energy, CT inputs must align with the respective 

voltage inputs. Be sure to consistently identify and match the two AC 

lines at two points: the main load center feed and the Envoy. Wire colors 

(typically black and red) may not always consistently identify Lines 1 and 

2. If in doubt, use a multimeter to check.

Summary of Contents for AC Combiner Box

Page 1: ...allation map for your records and to upload to Enlighten later G Note that installation of the Combiner has two parts To ensure successful device detection complete Part 2 after install ing any Enphase Microinverters and or Enphase AC Battery ies Note If needed you can find an installation map at the back of any Enphase Microinverter Quick Install Guide IMPORTANT This guide is for model XAM1 120 B...

Page 2: ...he dead front over the location of the removed breaker K Use a screwdriver and the two provided screws to secure the plate into place 3 Locking tabs INSTALLATION Part 1 You can complete Installation Part 1 before or after installing the PV system Choose a location for the AC Combiner Box A Install the AC Combiner Box in a readily accessible location The best practice is to install at least four fe...

Page 3: ...nto consideration the voltage drop rise and upstream breaker or fuse B The two DIN rail terminal blocks above the circuit breakers are the output connections Install the black wire into the lower terminal block and the red into the upper terminal block C Torque to 14 in lbs 1 6 Nm D Connect the neutral white to the neutral busbar E Connect the ground green or green yellow to the Ground busbar and ...

Page 4: ... do this you must create a protected route using conduit for the CT wires from the main load center to the Envoy S If you need to extend the wires refer to the Enphase Envoy S Installation and Operation Manual at enphase com support 7 Note Because of variance in load center design and main power feed there may not always be enough space to install consumption metering CTs DANGER Risk of electrocut...

Page 5: ... Device Communications LED flashes green while scanning solid green when all the devices you installed are communicating or solid amber if any devices are not communicating With both methods If the Device Communications LED remains solid amber see Troubleshooting b Verify System Configuration While still connected to the Envoy S with Installer Toolkit check the Over view screen for the following A...

Page 6: ...r network from the list of available networks If the wireless router does not support WPS you may be prompted to enter a password The Network Communica tions LED begins flashing green Within three minutes the Network Communications LED lights solid green indicating a successful connection to Enlighten If the Network Communications LED remains off or lights solid amber see Troubleshooting d Method ...

Page 7: ... steps Make sure that the broadband router is operational by checking that other devices at the site can access the network Be aware that metal enclosures or obstructions impede wireless communication If you cannot see your router or access point in the list on the Envoy or cannot maintain a connection it may be necessary to add a wireless repeater to extend the network range If you are using Wi F...

Page 8: ... Combiner Box read all instructions and cautionary markings in the technical description and on the equipment WARNING Use the circuit breakers in the Enphase AC Combiner Box only for serving Enphase equipment No other loads are allowed FCC Statement This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are ...

Reviews: