Technical Data
Installation and Operation Manual - COMTEC
®
/
OXITEC
®
DustEx
24
Doc.-ID: COM_OXI_Dust_11022020
A.2
Probe
Process gas temperature:
up to 600 °C (1112 °F)
Insertion depth:
KES-6001: 470
mm
KES-6002: 930
mm
Measuring principle:
Zirconium oxide for O
2
MXP for Co
e
Flue gas pressure:
-50 mbar to +50 mbar (-0.725 PSIG to +0.725 PSIG)
to atmosphere pressure
Flue gas flow velocity:
0 to 10 m/s, others on request
Ambient temperature:
-20 °C to +70 °C (-4 °F to +158 °F)
Maximum surface temperature
depending on the ambient
temperature:
Ambient temperature [°C]
Max. surface temperature [°C]
40 133
50 136
60 138
70 141
The given maximal surface temperatures 133°C to 141°C apply to the
above mentioned ambient temperatures.
Reaction time:
< 0.5 s (process flow velocity 10m/sec.)
T90:
< 5.0 s (with testgas)
Probe material:
stainless steel (SS316)
Ignition protection type:
II 2D Ex tb IIIC T133°C/T141°C Db
IP Code:
IP 6X
Certificate Number:
BVS 05 ATEX E 003 X
Power supply:
Through electronic unit
Probe dimensions:
on request