USER MANUAL
STM 550B / EMSIB - EASYFIT MULTISENSOR FOR IOT APPLICATIONS (2.4 GHZ BLE)
© 2020 EnOcean | www.enocean.com
F-710-017, V1.0
STM 550B / EMSIB User Manual | v1.3 | June 2020 | Page 82 / 115
9.5.29
TEMPERATURE_TX_INTERVAL
If temperature-controlled reporting has been enabled and the temperature meets the de-
fined threshold criteria then the resulting reporting interval will be determined by the regis-
ter TEMPERATURE_TX_INTERVAL shown in Figure 61 below.
TEMPERATURE_TX_INTERVAL (Default Setting: 0x003C)
Bit 15
Bit 14
…
Bit 1
Bit 0
TEMPERATURE INTERVAL
Figure 61
–
TEMPERATURE_TX_INTERVAL register
The encoding used by the TEMPERATURE INTERVAL bit field is shown in Table 47 below.
TEMPERATURE INTERVAL Temperature-based reporting interval
0x0000, 0x0001, 0x0002
Not supported (Do not use)
0x0003
3 seconds (minimum setting)
…
…
0x003C (Default)
60 seconds (default setting)
…
…
0xFFFF
65535 seconds (maximum setting)
Table 47
–
TEMPERATURE INTERVAL bit field encoding
The default reporting interval when the temperature meets the defined threshold criteria is
60 seconds. This can be reduced according to user requirements keeping in mind the en-
ergy balance.