9.5.19
THRESHOLD_CFG1
STM 550B can reduce the reporting interval based on the illumination of the solar cell, the
light illumination of the ambient level sensor, the temperature or the humidity as described
in chapter 2.3.
The use of these reduced reporting intervals is enabled by the THRESHOLD_CFG1 register
shown in Figure 51 below.
THRESHOLD_CFG1 (Default Setting: 0x00)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
HUMIDITY SENSOR TEMP SENSOR
LIGHT SENSOR
SOLAR CELL
Figure 51
–
THRESHOLD_CFG1 register
The encoding used by the SOLAR CELL bit field is shown in Table 31 below.
SOLAR CELL
Reporting interval reduction based on solar cell illumination
0b00 (Default)
Disabled (No reporting interval reduction)
0b01
Reserved (Do not use)
0b10
Enabled, Reporting interval reduction if light above threshold
0b11
Reserved (Do not use)
Table 31
–
SOLAR CELL bit field encoding
The encoding used by the LIGHT SENSOR bit field is shown in Table 32 below.
LIGHT SENSOR
Reporting interval reduction based on light sensor illumination
0b00 (Default)
Disabled (No reporting interval reduction)
0b01
Reserved (Do not use)
0b10
Enabled, Reporting interval reduction if light above threshold
0b11
Reserved (Do not use)
Table 32
–