![EnOcean B6221-K516 User Manual Download Page 73](http://html1.mh-extra.com/html/enocean/b6221-k516/b6221-k516_user-manual_2413678073.webp)
USER MANUAL
STM 550B / EMSIB - EASYFIT MULTISENSOR FOR IOT APPLICATIONS (2.4 GHZ BLE)
© 2020 EnOcean | www.enocean.com
F-710-017, V1.0
STM 550B / EMSIB User Manual | v1.3 | June 2020 | Page 73 / 115
9.5.20
THRESHOLD_CFG2
STM 550B can reduce the reporting interval based on the acceleration sensor status and
the magnet contact status as described in chapter 2.3.
The use of these reduced reporting intervals is enabled by the THRESHOLD_CFG2 register
shown in Figure 52 below.
THRESHOLD_CFG2 (Default Setting: 0x00)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
RFU
MC SENSOR
ACC SENSOR
Figure 52
–
THRESHOLD_CFG2 register
The encoding used by the ACC SENSOR bit field is shown in Table 35 below.
ACC SENSOR
Reporting interval reduction based on acceleration
0b00 (Default)
Disabled (No reporting interval reduction)
0b01
Reserved (Do not use)
0b10
Enabled, Reporting interval reduction if acceleration above threshold
0b11
Reserved (Do not use)
Table 35
–
ACC SENSOR bit field encoding
The encoding used by the MC SENSOR bit field is shown in Table 36 below.
MC SENSOR
Reporting interval reduction based on magnet contact status
0b00 (Default)
Disabled (No reporting interval reduction)
0b01
Enabled, Reporting interval reduction if contact is open
0b10
Enabled, Reporting interval reduction if contact is closed
0b11
Reserved (Do not use)
Table 36
–
MC SENSOR bit field encoding