Engelmann Sensor GmbH,  Rudolf-Diesel-Straße 24-28 , 69168 Wiesloch-Baiertal, Germany
Phone.: +49 (0)6222-9800-217 , Fax: +49 (0)6222-9800-50, E-Mail: [email protected],  www.engelmann.de

Article-No.  1080700010 - 2011-04-01

Page 1

Calculator with Ultrasonic

DE-09-MI004-PTB018 / 22.72/09.01

Installation and Operating Instructions

4.1  Safety instructions

 

Look out for sharp edges (pipes, 

fl

 anges).

 

Installation and deinstallation should only be carried out by 

quali

fi

 ed technical personnel.

 

Mounting and dismounting may only be carried out without 

pressure in the heating or cooling system.

 

After installation a hydraulic pressure test should be carried out 

using cold water to check for leaks.

 

For safe operation, the instrument must be used only under the 

stated operating conditions (see section 15: Technical Data). 

In addition, the guarantee only applies if the allowed operating 

conditions have been adhered to.

 

The security seals may not be damaged, otherwise the guaran-

tee is no longer valid.

 

Protection against lightning is not guaranteed; lightning protec-

tion must be implemented at the installation site.

4    Mounting the Flow Sensor

1  Application and Function

The 

S

ENSO

S

TAR

®

2C US 

Ultrasonic Meter is designed for the 

measurement of heat and cooling energy. The connected 

fl

 ow sen-

sor must be installed in the return 

fl

 ow. Optionally, the meter can be 

set in the factory to measure 

fl

 ow volume in the forward 

fl

 ow (state 

when ordering – not for cooling meters!)

.

The instrument has an optical interface for read-out and parameteri-

zation. Optionally, the instrument can be equipped at the factory with 

an M-bus interface, up to two pulse outputs (for energy and volume) 

or alternatively with two pulse inputs. It is also possible to power the 

instrument using a power pack (not available in combination with 

M-bus power supply.)

4.2  General information on the fl ow sensor

 

Be careful not to pick up the 

fl

 ow sensor on the plastic housing. 

Always pick up and carry the sensor on the threaded or 

fl

 anged 

connections.

 

All cables must be laid at a minimum distance of 20 cm to high-

voltage current cables.

 

If more than one sensor is being installed in a unit, care must 

be taken to be sure that all the meters have the same installati-

on conditions.

 

Overpressure must be applied in order to avoid cavitation in the 

complete measurement range; this means at least 1 bar up to 

qp and approx. 3 bar at overload qs (speci

fi

 cations for approx. 

80°C).

 

The 

fl

 ow sensor left the factory in conformance with all ap-

plicable safety regulations. Calibration, maintenance, repairs 

and the exchange of parts may only be carried out by quali

fi

 ed 

technical personnel who are familiar with the dangers involved. 

Further technical support can be provided by the manufacturer 

upon request. Veri

fi

 cation seals on the 

fl

 ow sensor may not be 

damaged or removed – otherwise the guarantee and veri

fi

 ca-

tion of the instrument no longer apply! 

4.3  Technical data of the fl ow sensor

 

Environmental class A (EN1434), for indoor installation 

 

Mechanical class M1*)

 

Electromagnetic class E1*) 

*) as per Measurement Instrument Directive 2004/22/EU

2     Scope of Delivery

• 

Calculator 

S

ENSO

S

TAR

®

2C US

• 

Installation kit: 1 O-ring; 5 sel

fl

 ock seals + 5 sealing wires;

  

2 2 dowels for direct screw mounting (if this

 

technique is used - see section 9.3) 

• 

Installation and Operating Instructions

• 

 

2 gaskets for the 

fl

 ow sensor

3

     

General Information

All details and speci

fi

 cations listed in instrument data sheet or in 

these installation and operating instructions must be adhered to: 
• The valid statutory provisions and standards for the application of 

instrument for the measurement of heat energy are: EN1434 parts 

1+6 and the Directive 2004/22/EC with annexes I and MI-004.

• The instrument may only be installed or exchanged by quali

fi

 ed 

and authorized technical personnel.

• The regulations for electrical installations must be adhered to
• The applicable veri

fi

 cation regulations and periods for the country 

in which the instrument is to be installed must be observed.

• The instrument left the factory in conformance with all applicable 

safety regulations.

• The instrument must be stored and transported frost-free. The 

temperature during storage or transport may not fall below 1°C. 

The relative humidity during storage and transport may not be 

more than 80%.

• The instrument identi

fi

 cation and the seals required for veri

fi

 cation 

of the instrument must not be damaged or removed – otherwise 

the guarantee and veri

fi

 cation of the instrument no longer apply!

• To clean the instrument (only if necessary) use a slightly moist 

(not dripping wet!) cloth.

• To protect against damage and dirt the instrument should only be 

removed from the packaging directly before installation.

• All electrical connections of the instrument must be laid at a 

minimum distance of 50 cm

 to sources of electromagnetic 

interference (switches, controllers, pumps, etc.)

• All instrument connections must be laid at a 

minimum distance 

of 10 cm

 to other current-carrying wires.

Summary of Contents for SensoStar 2C Ultrasonic

Page 1: ...to qp and approx 3 bar at overload qs specifications for approx 80 C The flow sensor left the factory in conformance with all ap plicable safety regulations Calibration maintenance repairs and the exchange of parts may only be carried out by qualified technical personnel who are familiar with the dangers involved Further technical support can be provided by the manufacturer upon request Verificati...

Page 2: ...d contact class OA as per EN1434 2 2007 passive electronic current sink open collector class OC as per EN1434 2 2007 Installation point standard in return flow optional in forward flow only for heat meter calculator must be set in factory Mounting position Heat meter any Mounting position Cooling meter see section 6 Installation for Cooling Applica tions 4 4 Small flow sensors Nominal flow q p Ins...

Page 3: ...50 22 G 1 1 4 B 10 16 200 48 G 2 B 10 16 300 48 G 2 B For the short models with length 150 mm the temperature range for the medium lies between 20 0 C and 130 0 C 4 7 Premium Flow Sensors Please note that the normal flow sensors may not be used with salt water Upon request we can provide salt water resistant versions of the flow sensors qp m h PN bar DN a b Øc Ød Øe No of holes f g 3 5 25 25 260 5...

Page 4: ...o C 10 DN Black housing of transducers 5 Integration in the Heating System Please inspect and check all dimensions to be sure that there is sufficient space in the intended location for installation of the flow sensor No minimum straight pipe sections are required upstream or downstream for the flow sensor If the flow sensor is being installed in the common return flow of two heat systems e g heat...

Page 5: ...ification must always be installed in the return flow The temperature sensors are not to be installed within the influence of other sources of heat Do not kink lengthen or shorten the cables Cables that are too long should not be rolled up tightly into an air core coil The cables should either be laid out unordered or rolled up loosely into a wide coil which can be turned and tied into an 8 Mounti...

Page 6: ...for connection to an additional system For connection of meters with open collectors atten tion must be paid to the polarity Polarity is not important for these connections so the wires can be clamped arbitrarily When the M bus network is in operation a triangle will appear in the lower right corner of the display Power supply from the M bus network is functioning Connection of M bus Connection of...

Page 7: ... 9 Selectable customer set calculator no secondary address factory setting is the serial no 10 Tariff register1 Values alternating with tariff register and criteria 2 3 11 Tariff register 2 Values alternating with tariff register and criteria 2 3 12 Momentary reading of the pulse counter1 alternating with the pulse value 2 3 13 Momentary reading of the pulse counter 2 alternating with the pulse va...

Page 8: ...pulse value is automatically determined by the second to last place of the volume display The pulse units are identical to the units of the volume display Example 1 Display 12345 678 m3 pulse value for volume pulse output 0 01 m3 pulse Example 2 Display 12345678 l pulse value for volume pulse output 10 l pulse Display examples Description of example in tariff register 1 either the energy or the ti...

Page 9: ...he optical interface using the Engelmann Monitor software They can also be set using the display The primary address is the M bus address displayed in the 2nd level technician s loop in menu item 6 M bus address primary address The secondary address is the customer identification no and can be selected under menu item 9 Selectable customer set calculator no in the first level the main loop If a cu...

Page 10: ...se inputs Data storage E2 PROM daily Maximal value storage 3 each for flow and power Billing dates annual billing date selectable from dd mm to dd mm Monthly values 24 monthly values readable Protection class housing IP65 EMC class E1 Mechanical environment class M1 Pulse input device microcontroller CMOS input class IB as per EN1434 2 2007 Dimensions length x width x height 198 mm x 123 7 mm x 45...

Page 11: ...rement is carried out every 30 seconds for standard instruments Example sensors switched Error Error code Binary display LCD Check sum fault E2PROM fault Reset Reference sensor fault Return fl ow senso fault Sensors switched Forward fl ow sen fault Error display hexadeci mal LCD When an error occurs with the exception of the reset and sensors switched error the instrument must be exchanged and sen...