background image

Engelmann

T h e   h e a t   m e t e r   s p e c i a l i s t s

®

Engelmann Sensor GmbH,  Rudolf-Diesel-Straße 24-28 , 69168 Wiesloch-Baiertal, Germany
Phone.: +49 (0)6222-9800-217 , Fax: +49 (0)6222-9800-50, E-Mail: [email protected],  www.engelmann.de

Article-No.  1080700010 - 2011-04-01

Page 9

13 

Interfaces and Options

13.1 

Optical (infrared) interface 

In order to be able to communicate with a 

S

ENSO

S

TAR

®

2C

 ins-

trument, an optocoupler must be connected to the USB or serial 

interface of the PC. The optocoupler (USB or serial interface) and 

the Engelmann

®

Monitor software are available as options.

The optical (infrared) interface is activated by pressing the 
Engelmann pushbutton.

If within 60 seconds neither a valid telegram is received now the 

pushbutton pressed again, then the interface is deactivated.

13.2 M-bus 

interface

An M-bus interface is also available as a built-in option for the 

S

ENSO

S

TAR

®

2C

 (must be stated when ordering).  An inst-

rument with an M-bus interface is supplied with power via the 

M-bus network (no galvanic separation). The number of read-outs 

via the M-bus interface per instrument per day is unlimited.
The valid standards for the M-bus protocol are EN13757-2 and 

13757-3 and the M-bus recommendation (Version 4.8 from Nov. 

1997) with the standard IEC 870 part 1,2 and 4.

Notes on installation:

• 

Each end instrument is only protected against high voltage 

up to the maximal allowed bus voltage (±50V). Additional 

protective measures must be provided by the level converter.

• 

The installation of an instrument in an M-bus network may 

only be carried out by authorized, quali

fi

 ed technical 

personnel.

• 

Attention must be paid to ensure that the cable lengths and 

cable cross-sections in the bus network are appropriate for 

the baud rate of the end instrument (2400 baud).

• 

Recommended cable type: 

Telephone cable J-Y(ST) Y2 x 2 x 0.8 mm²

S

ENSO

S

TAR

®

2C

 instruments with the M-bus option can be 

addressed primarily or secondarily. 
Both addresses can be set via the optical interface using the 

Engelmann

®

Monitor software. They can also be set using the 

display. 
The primary address is the M-bus address displayed in the 2nd 

level (technician’s loop) in menu item 6) ‘M-bus address (primary 

address)’. 
The secondary address is the customer identi

fi

 cation no. and can 

be selected under menu item 9) ‘Selectable customer-set 

calculator no.’ ‚ in the 

fi

 rst level (the main loop).

If a customer no. has not been identi

fi

 ed, the serial no. is 

displayed. This is the factory setting. 

13.3  Settings of the Datalogger

The datalogger is an optional additional function for meters and 

calculators which must be speci

fi

 ed in the original order (instru-

ments cannot be retro

fi

 tted).

The Engelmann datalogger makes it possible to record consump-

tion data and the individual meter values in the internal storage 

module in freely selectable time intervals. The recorded data can 

be stored in various data formats, for example for analysis of 

peak values in order to optimize cost-effective supply of heat.

The datalogger can be read out either via the optical interface or 

via M-bus, so that the data can be used for individual analysis. 

The Engelmann datalogger is a ring buffer. The current values 

are always stored; this means that when the memory is full, the 

oldest values are written over by each new piece of data. 

The storage capacity is up to 10,589 values.

The software “Engelmann Datalogger“ reads out only one meter 

at a time, which is addressed using the set primary address. 

If only one meter is at hand, the address 254 can be used.

The following parameters can be individually set for recording, 

singly or jointly, using the software “Engelmann Datalogger“:

• 

time (is always stored)

• heat 

energy

• cooling 

energy

• volume

• power

• 

fl

 ow

• forward 

fl

 ow temperature

• return 

fl

 ow temperature

• temperature 

difference

The meters values can be measured at the following freely 

selectable time intervals:

• 

  1 minute

• 10 

minutes

• 15 

minutes

• 30 

minutes

• 60 

minutes

• 

  3 hours

• 

  6 hours

• 12 

hours

• 24 

hours

Depending on the con

fi

 guration, the datalogger can store 

between 2117 and 10,589 sets of data.

Note

:

All previous stored values are lost (deleted) upon

reparameterization!

Summary of Contents for SensoStar 2C Ultrasonic

Page 1: ...to qp and approx 3 bar at overload qs specifications for approx 80 C The flow sensor left the factory in conformance with all ap plicable safety regulations Calibration maintenance repairs and the exchange of parts may only be carried out by qualified technical personnel who are familiar with the dangers involved Further technical support can be provided by the manufacturer upon request Verificati...

Page 2: ...d contact class OA as per EN1434 2 2007 passive electronic current sink open collector class OC as per EN1434 2 2007 Installation point standard in return flow optional in forward flow only for heat meter calculator must be set in factory Mounting position Heat meter any Mounting position Cooling meter see section 6 Installation for Cooling Applica tions 4 4 Small flow sensors Nominal flow q p Ins...

Page 3: ...50 22 G 1 1 4 B 10 16 200 48 G 2 B 10 16 300 48 G 2 B For the short models with length 150 mm the temperature range for the medium lies between 20 0 C and 130 0 C 4 7 Premium Flow Sensors Please note that the normal flow sensors may not be used with salt water Upon request we can provide salt water resistant versions of the flow sensors qp m h PN bar DN a b Øc Ød Øe No of holes f g 3 5 25 25 260 5...

Page 4: ...o C 10 DN Black housing of transducers 5 Integration in the Heating System Please inspect and check all dimensions to be sure that there is sufficient space in the intended location for installation of the flow sensor No minimum straight pipe sections are required upstream or downstream for the flow sensor If the flow sensor is being installed in the common return flow of two heat systems e g heat...

Page 5: ...ification must always be installed in the return flow The temperature sensors are not to be installed within the influence of other sources of heat Do not kink lengthen or shorten the cables Cables that are too long should not be rolled up tightly into an air core coil The cables should either be laid out unordered or rolled up loosely into a wide coil which can be turned and tied into an 8 Mounti...

Page 6: ...for connection to an additional system For connection of meters with open collectors atten tion must be paid to the polarity Polarity is not important for these connections so the wires can be clamped arbitrarily When the M bus network is in operation a triangle will appear in the lower right corner of the display Power supply from the M bus network is functioning Connection of M bus Connection of...

Page 7: ... 9 Selectable customer set calculator no secondary address factory setting is the serial no 10 Tariff register1 Values alternating with tariff register and criteria 2 3 11 Tariff register 2 Values alternating with tariff register and criteria 2 3 12 Momentary reading of the pulse counter1 alternating with the pulse value 2 3 13 Momentary reading of the pulse counter 2 alternating with the pulse va...

Page 8: ...pulse value is automatically determined by the second to last place of the volume display The pulse units are identical to the units of the volume display Example 1 Display 12345 678 m3 pulse value for volume pulse output 0 01 m3 pulse Example 2 Display 12345678 l pulse value for volume pulse output 10 l pulse Display examples Description of example in tariff register 1 either the energy or the ti...

Page 9: ...he optical interface using the Engelmann Monitor software They can also be set using the display The primary address is the M bus address displayed in the 2nd level technician s loop in menu item 6 M bus address primary address The secondary address is the customer identification no and can be selected under menu item 9 Selectable customer set calculator no in the first level the main loop If a cu...

Page 10: ...se inputs Data storage E2 PROM daily Maximal value storage 3 each for flow and power Billing dates annual billing date selectable from dd mm to dd mm Monthly values 24 monthly values readable Protection class housing IP65 EMC class E1 Mechanical environment class M1 Pulse input device microcontroller CMOS input class IB as per EN1434 2 2007 Dimensions length x width x height 198 mm x 123 7 mm x 45...

Page 11: ...rement is carried out every 30 seconds for standard instruments Example sensors switched Error Error code Binary display LCD Check sum fault E2PROM fault Reset Reference sensor fault Return fl ow senso fault Sensors switched Forward fl ow sen fault Error display hexadeci mal LCD When an error occurs with the exception of the reset and sensors switched error the instrument must be exchanged and sen...

Reviews: